background image

 

 S&C Instruction Sheet 1023-550    13

Miscellaneous Problems

SCADA commands are ignored by the capacitor control

Follow these steps to check SCADA command performance:

STEP 1. 

Check the SCADA CONTROL LED display. To operate the bank remotely, the 
faceplate REMOTE LED display must be lit. If it is not, press the SCADA CONTROL 
CHANGE button.

STEP 2. 

Check for control power. See the “LCD Display Problems” section on page 9.

STEP 3. 

Check the RTU address. On Page 1 of the 

Communications Setup

 screen, check 

which communications RTU address is used by this control. Make sure the SCADA 
master station is sending commands for this control to the correct address.

STEP 4. 

Check the baud rate. On Page 2 of the 

Communications Setup

 screen, make sure 

the baud rate is correct for your communications equipment. For modems, the 
baud rate should match the baud rate used by the SCADA master station.

STEP 5. 

Check your communications hardware. See the appropriate communication  
instructions for more information.

Capacitor bank switch does not operate

Follow these steps to check bank switch operation:

STEP 1. 

Make sure the faceplate LOCAL and MANUAL LED displays are both lit. If the 
LOCAL LED display is off, press the SCADA CONTROL CHANGE button. If the 
MANUAL LED display is off, press the OPERATION MODE CHANGE button, then 
press the CLOSE or OPEN button.

STEP 2. 

Check the faceplate CLOSE/OPEN LED displays. If the OPEN LED display is 
blinking slowly, the Reclose Block delay is operating. Wait until it stops blinking, 
then try switching the bank again. If both LED displays are off, see the “Incompatible 
Ident” section on page 11.

STEP 3. 

Check the line voltage level. Make sure the line voltage is not below the minimum 
required to switch the capacitor bank.

STEP 4. 

Check the Capacitor Bank Switch Control Pulse Time. Connect the computer to 
the control and start the IntelliLink software. Check that the 

Capacitor Bank 

Switch Control Pulse Time

 setpoint (on Page 2 of the 

Setup>General

 screen) is 

long enough. See Instruction Sheet 1023-530, “S&C IntelliCap® Plus Automatic 
Capacitor Control: 

Setup

,” for more information.

STEP 5. 

Check the wiring. The wiring between the capacitor control and a bank switch may 
be damaged or defective.

STEP 6. 

Check the capacitor bank primary switch(es). The capacitor bank switch(es) may 
be malfunctioning.

Some (but not all) capacitor bank switches do not operate

STEP 1. 

Check the line-voltage level. Make sure the line voltage is not below the minimum 
required to switch the capacitor bank.

STEP 2. 

Check the Capacitor Bank Switch Control Pulse Time. Connect the computer to 
the capacitor control and start the IntelliLink software. Check that the 

Capacitor 

Bank Switch Control Pulse Time

 setpoint (on Page 2 of the 

Setup>General

 

screen) is long enough. See Instruction Sheet 1023-530, “S&C IntelliCap® Plus 
Automatic Capacitor Control: 

Setup

,” for more information.

STEP 3. 

Check the wiring. The wiring between the capacitor control and a bank switch may 
be damaged or defective.

STEP 4. 

Check the capacitor bank primary switch(es). The capacitor bank switch(es) may 
be malfunctioning.

Содержание IntelliCap Plus

Страница 1: ...acement Instructions and Labels 4 Safety Precautions 5 Troubleshooting Overview Applicable Software 6 LCD Screen 6 IntelliLink Setup Software 6 Electrical Diagrams 6 Test Points 7 Tools Required 7 Bas...

Страница 2: ...s standard conditions of sale as set forth in Price Sheets 150 and 181 applies to the S C IntelliCap Plus Automatic Capacitor Control except that the first paragraph of the said warranty is replaced...

Страница 3: ...urchaser or end user all manufacturer s warranties that apply to such major components Warranty of equipment services packages is contingent upon receipt of adequate informa tion on the user s distrib...

Страница 4: ...y if instructions including recommended precautions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not...

Страница 5: ...utomatic Capacitor Control must be restricted only to Qualified Persons 2 SAFETY PROCEDURES Always follow safe operating procedures and rules Always maintain proper clearance from energized components...

Страница 6: ...ntrol Before attempting to access an existing switch installation check carefully for visible or audible signs of electrical or physical malfunction do this before touching or operating the switch con...

Страница 7: ...minate the possibility of software malfunction reload the operating software into the control STEP 1 Connect a PC loaded with IntelliLink Setup Software to the Local Comm Port on the faceplate STEP 2...

Страница 8: ...the Manual setting This will prevent any automatic operation Follow these steps to check a blown load fuse STEP 1 With the faceplate buttons change the operation mode to the Manual state STEP 2 Remove...

Страница 9: ...blank STEP 1 Check for ac power to the control Check for ac voltage between test points 2 Ac Line and 3 Neutral Return below the faceplate If there is no voltage a For controls with a meter base make...

Страница 10: ...Voltage Change Margin setpoint is greater than the difference between the High Voltage Override Value data and the Low Voltage Override Value data HiLoVoltLockout The control has locked out the bank b...

Страница 11: ...the port on the side of the enclosure Check that the cable is plugged into the correct port on the computer usually COM1 on portable computers STEP 3 Check the optical coupler power source If using an...

Страница 12: ...tribution alter the pure sine wave RMS voltmeters do not account for this so their readings are often inaccurate True RMS is a repeatable voltage result independent of waveform harmonic content Theref...

Страница 13: ...king slowly the Reclose Block delay is operating Wait until it stops blinking thentryswitchingthebankagain IfbothLEDdisplaysareoff seethe Incompatible Ident section on page 11 STEP 3 Check the line vo...

Страница 14: ...e Setup General screen The capacitor control does not switch the bank if doing so would cause a Voltage Override condition See Instruction Sheet 1023 530 S C IntelliCap Plus Automatic Capacitor Contro...

Страница 15: ...trol Setup STEP 3 If the IntelliLink software is already running click on the Operation button from any screen Operation Screen Figure 2 The Operation screen for a var control The Operation screen inc...

Страница 16: ...trol does not have neutral sensing installed this field displays n a Neutral Sensor Fundamental This field displays the fundamental 60 Hz component of the neutral sensing value when installed Neutral...

Страница 17: ...age in the Current Flow Direction field and subtracts 180 degrees from the phase angle Power kVA var controls only This is the present kVA level measured at the location of the current sensor Power kW...

Страница 18: ...ctive is displayed the condition presently exists Occurred at The most recent time the alarm became active Last Cleared at The most recent time the alarm became inactive The control records the date a...

Страница 19: ...age controls only For controls with neutral current neutral voltage sensing this field displays Active when the neutral current neutral voltage is above the alarm level for the duration of the applica...

Страница 20: ...ll lockout again and in Automatic mode it will attempt Corrective Action and Retry if these features are enabled Reset Alarms Request The Reset All Alarms request attempts to clear all trouble and err...

Страница 21: ...he normal direction this field displays Normal If unusual circuit switching conditions cause the direction of power flow to reverse the field displays Reverse Corr Phase Angle var controls only This i...

Страница 22: ...larming This is the component or components of the neutral current used to trigger the Neutral Sensing alarm Voltage Harmonics This column shows the most recently calculated harmonics for the single p...

Страница 23: ...le PCVD116S Comments This field includes miscellaneous information about the control and IntelliLink software For example if the IntelliLink software is older than the control software this field incl...

Страница 24: ...in the log The events are listed in reverse chronological order This screen includes the following fields Timestamp This is the date and time the event occurred Event The message in this field describ...

Страница 25: ...Voltage Outside Operating Range The line voltage is outside the range for the Nominal Operating Voltage setpoint noted on Page 3 of the Setup General screen Line Voltage Within Operating Range The li...

Страница 26: ...eared A reverse current condition has cleared For controls with neutral sensing the additional event messages are Neutral Sensor Alarm Active The level of neutral current or neutral voltage has caused...

Отзывы: