background image

16    S&C Instruction Sheet 1023-550 

Using IntelliLink Software to Locate Problems

Model Number

This field shows the model number of this control.

Control Software Revision

This field shows the S&C name of the control software version present in this control, for 
example PCSD100S.

Serial Number

This field shows the serial number of the capacitor control.

Alarm Status button

This button takes you to the 

Alarm Status

 screen. When any alarms are presently active, 

the text on the button flashes.

Present Conditions

Except for the 

Temperature

 value, these fields are the true RMS amplitude measurements 

for the three phases on the feeder. The capacitor control takes a measurement  
every 0.3 seconds. It then averages four measurements and displays the 1.2-second  
averaged value. For a more detailed explanation of these fields, see Instruction Sheet 1023- 
530, “S&C IntelliCap® Plus Automatic Capacitor Control: 

Setup

.”

The 

Temperature

 value is the present air temperature. The temperature sensor is located 

on the bottom of the control enclosure.

Neutral Sensor (Total RMS)

This field displays the total RMS value for neutral sensing, when installed. Neutral  
sensing alarming uses the Total RMS value when the 

Neutral Sensing Alarming (Current 

or Voltage)

 setpoint on the IntelliLink 

Setup>Neutral Sensing

 screen, is set to 

Total RMS

 

mode. When the control does not have neutral sensing installed, this field displays “n/a.”

Neutral Sensor (Fundamental)

This field displays the fundamental (60-Hz) component of the neutral sensing value, when 
installed. Neutral sensing alarming uses the fundamental value when the 

Neutral  

Sensing Alarming (Current or Voltage)

 setpoint on the IntelliLink 

Setup>Neutral 

Sensing

 screen is set to 

Fundamental

 mode. When the control does not have neutral  

sensing installed this field displays “n/a.”

Voltage Override

This field shows whether a voltage-override condition is presently active.

SCADA Override

This field shows whether the 

SCADA Override

 feature is in the 

Enabled

 state via SCADA  

command.

Error Conditions

When the control detects an alarm or an error condition, this field displays the message 
“See Alarm Status.” When this message is present, see the 

Alarm Status

 screen for more 

information.

Current Flow Direction, Power kvars, and Power Factor (var controls 
only)

The control measures the phase angle between the voltage and current waveforms. If the 
phase angle is between ±90 degrees, the 

Current Flow Direction

 field shows “Normal.” 

The control calculates and displays the measured power factor and measured 3-phase 
kvars. For controls with single-phase sensing, the displayed power kvars value is the  
calculated single-phase kvars value times three.

When the phase angle is between -90 degrees (the same as +270 degrees) and 0 degrees, 

the power factor and kvars are given a negative sign, which indicates that the current wave-
form is leading the voltage waveform.

Содержание IntelliCap Plus

Страница 1: ...acement Instructions and Labels 4 Safety Precautions 5 Troubleshooting Overview Applicable Software 6 LCD Screen 6 IntelliLink Setup Software 6 Electrical Diagrams 6 Test Points 7 Tools Required 7 Bas...

Страница 2: ...s standard conditions of sale as set forth in Price Sheets 150 and 181 applies to the S C IntelliCap Plus Automatic Capacitor Control except that the first paragraph of the said warranty is replaced...

Страница 3: ...urchaser or end user all manufacturer s warranties that apply to such major components Warranty of equipment services packages is contingent upon receipt of adequate informa tion on the user s distrib...

Страница 4: ...y if instructions including recommended precautions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not...

Страница 5: ...utomatic Capacitor Control must be restricted only to Qualified Persons 2 SAFETY PROCEDURES Always follow safe operating procedures and rules Always maintain proper clearance from energized components...

Страница 6: ...ntrol Before attempting to access an existing switch installation check carefully for visible or audible signs of electrical or physical malfunction do this before touching or operating the switch con...

Страница 7: ...minate the possibility of software malfunction reload the operating software into the control STEP 1 Connect a PC loaded with IntelliLink Setup Software to the Local Comm Port on the faceplate STEP 2...

Страница 8: ...the Manual setting This will prevent any automatic operation Follow these steps to check a blown load fuse STEP 1 With the faceplate buttons change the operation mode to the Manual state STEP 2 Remove...

Страница 9: ...blank STEP 1 Check for ac power to the control Check for ac voltage between test points 2 Ac Line and 3 Neutral Return below the faceplate If there is no voltage a For controls with a meter base make...

Страница 10: ...Voltage Change Margin setpoint is greater than the difference between the High Voltage Override Value data and the Low Voltage Override Value data HiLoVoltLockout The control has locked out the bank b...

Страница 11: ...the port on the side of the enclosure Check that the cable is plugged into the correct port on the computer usually COM1 on portable computers STEP 3 Check the optical coupler power source If using an...

Страница 12: ...tribution alter the pure sine wave RMS voltmeters do not account for this so their readings are often inaccurate True RMS is a repeatable voltage result independent of waveform harmonic content Theref...

Страница 13: ...king slowly the Reclose Block delay is operating Wait until it stops blinking thentryswitchingthebankagain IfbothLEDdisplaysareoff seethe Incompatible Ident section on page 11 STEP 3 Check the line vo...

Страница 14: ...e Setup General screen The capacitor control does not switch the bank if doing so would cause a Voltage Override condition See Instruction Sheet 1023 530 S C IntelliCap Plus Automatic Capacitor Contro...

Страница 15: ...trol Setup STEP 3 If the IntelliLink software is already running click on the Operation button from any screen Operation Screen Figure 2 The Operation screen for a var control The Operation screen inc...

Страница 16: ...trol does not have neutral sensing installed this field displays n a Neutral Sensor Fundamental This field displays the fundamental 60 Hz component of the neutral sensing value when installed Neutral...

Страница 17: ...age in the Current Flow Direction field and subtracts 180 degrees from the phase angle Power kVA var controls only This is the present kVA level measured at the location of the current sensor Power kW...

Страница 18: ...ctive is displayed the condition presently exists Occurred at The most recent time the alarm became active Last Cleared at The most recent time the alarm became inactive The control records the date a...

Страница 19: ...age controls only For controls with neutral current neutral voltage sensing this field displays Active when the neutral current neutral voltage is above the alarm level for the duration of the applica...

Страница 20: ...ll lockout again and in Automatic mode it will attempt Corrective Action and Retry if these features are enabled Reset Alarms Request The Reset All Alarms request attempts to clear all trouble and err...

Страница 21: ...he normal direction this field displays Normal If unusual circuit switching conditions cause the direction of power flow to reverse the field displays Reverse Corr Phase Angle var controls only This i...

Страница 22: ...larming This is the component or components of the neutral current used to trigger the Neutral Sensing alarm Voltage Harmonics This column shows the most recently calculated harmonics for the single p...

Страница 23: ...le PCVD116S Comments This field includes miscellaneous information about the control and IntelliLink software For example if the IntelliLink software is older than the control software this field incl...

Страница 24: ...in the log The events are listed in reverse chronological order This screen includes the following fields Timestamp This is the date and time the event occurred Event The message in this field describ...

Страница 25: ...Voltage Outside Operating Range The line voltage is outside the range for the Nominal Operating Voltage setpoint noted on Page 3 of the Setup General screen Line Voltage Within Operating Range The li...

Страница 26: ...eared A reverse current condition has cleared For controls with neutral sensing the additional event messages are Neutral Sensor Alarm Active The level of neutral current or neutral voltage has caused...

Отзывы: