S&C Instruction Sheet 1023-550 25
Hardware Manual Override Enabled
The faceplate OPERATION MODE switch was set to
Manual
mode.
Hardware Remote SCADA Disabled
The faceplate SCADA CONTROL switch was set to
Local
mode.
Hardware Remote SCADA Enabled
The faceplate SCADA CONTROL switch was set to
Remote
mode.
High-/Low-Voltage Band Active
The
Bank Voltage Rise + Margin
value is greater than the difference between the
High-
Voltage Override Value
setpoint and the
Low-Voltage Override Value
setpoint.
High-/Low-Voltage Band Cleared
The
Bank Voltage Margin
value, the
High-Voltage Override Value
setpoint,
and the
Low-Voltage Override Value
setpoint are compatible.
High-/Low-Voltage Band Lockout
The control has blocked further automatic operation of the bank due to a Bank Voltage
Margin Value error.
IntelliLink Manual Close
The user sent a command from the
Operation
screen to switch the bank in.
IntelliLink Manual Open
The user sent a command from the
Operation
screen to switch the bank out.
Line Voltage Outside Operating Range
The line voltage is outside the range for the
Nominal Operating Voltage
setpoint noted
on Page 3 of the
Setup>General
screen.
Line Voltage Within Operating Range
The line voltage is within the range for the
Nominal Operating Voltage
setpoint noted on
Page 3 of the
Setup>General
screen.
Max Daily Auto Cycles Cleared
The
Max Daily Auto Cycles Reached
condition has cleared. The condition is cleared at
the beginning of each calendar day, when all cycle counters are reset on the
Operation
Counters
screen, and when the control tries to take corrective action after a
Neutral
Current/Neutral Voltage
alarm.
Max Daily Auto Cycles Reached
The number of automatic switching cycles has reached the
Maximum Automatic Control
Cycles Per Day
setpoint noted on Page 2 of the
Setup>General
screen.
Request Caps. In Ckt.
The capacitor control sent a command to switch in the capacitor bank.
Request Caps. Out of Ckt.
The capacitor control sent a command to switch out the capacitor bank.
System Power-Up
Power was restored to the capacitor control.
Temperature Sensor Bad
The temperature sensor is reading outside of its range or may be faulty.
Using IntelliLink Software to Locate Problems