TY-JS-220308-004

13

normal state in 6s and is restored to factory settings.

3.

Press

key to show t1

Press ▼ key again to show room temperature (Meanwhile D1 is flashing, displaying room
temperature)

Press

key again to show t2 and press

key again to show flow rate 1.(Unit: L/min)

Press

key again to show t3 and press

key again to show flow rate 2.(Unit: L/min)

Press

key again to exit display or to restore water temperature display in 6 seconds if

no key is pressed.

4.

Alarm function

(1) Alarm Display:

When alarm occurs, the error code and the water temperature will be alternately displayed.

E1

E2

E3

E4

E5

E6

E7

Ultra-high

room

temperature

Ultra-high

water

temperature

Ultra-low

water

temperature

Room

temperature

sensor

failure

Water

temperature

sensor

failure

Flow

rate

1

alarm

Flow

rate

2

alarm

(2) To suspend the alarm:

In alarming state, the alarm sound could be suspended by pressing any button, but the

alarm display remains until the alarm condition is eliminated.

5.

General settings adjustment

Press SET button

SET

to enter the user-defined state. Meanwhile, D1 flashes and

indicates that the controller is in parameter setup status.

(1)

Under the intelligent mode, the control panel displays the temperature difference

between the temperature of water and room (Factory setting is -2).

(2)

At this moment, press ▲▼ key to change settings. After modifying the value, press

the ENTER button (RST) to save and exit, then the new parameters take effect, or

press SET key (SET) to exit without saving the parameters. If there is no more action

within 20 seconds, the chiller will automatically exit the modifying status without saving

the new parameters.

6.

Advanced parameters adjustment examples

Order Code

Items

Value in Case 1 Value in Case 2

1

F0

Temperature setting

25

2

F1

Temperature Difference

Values

-3

3

F2

Refrigeration return

difference

0.5

2.0

4

F3

Way of control

1

0

5

F4

Alarm for over high water

temperature

15

5

6

F5

Alarm for over low water

temperature

15

10

7

F6

Alarm for over high room

temperature

45

45

Содержание CW-5000 Series

Страница 1: ...TY JS 220308 004 1 CW 5000 5200 Industrial Circulating Chiller Installation Operation Instructions...

Страница 2: ...rly so that you can refer to it whenever you need information This manual is not a quality guarantee Our company reserves the right to the interpretation of the correction of misprint and improperly d...

Страница 3: ...TENTS Notice 4 I Overview 7 II Model Illustration 7 III Product Outlines Parts 8 IV Installation 10 V Operating States Parameters Adjustment 12 VI Alarm Output Terminal 14 VII Maintenance 15 VIII Simp...

Страница 4: ...It is not permitted to install the chiller in dangerous places with inflammable gas Electrical connection a The power supply must conform to the standard indicated in the nameplate or the manual b Use...

Страница 5: ...uideline Transportation with liquid is prohibited The equipment is not allowed to be transported with liquid to prevent internal pipeline leakage Transport a The equipment should be fixed firmly befor...

Страница 6: ...rease and the power consumption will increase and the alarm will not work properly Equipment surface cleaning a Please use cleaning agents that are non corrosive to metals and plastics b Please keep t...

Страница 7: ...chiller the refrigerant in the evaporator coil absorbs the heat of the return water and vaporizes into steam The compressor continuously extracts the generated steam from the evaporator and compresses...

Страница 8: ...TY JS 220308 004 8 III Product Outlines Parts TEMPERATUR E CONTROLLER POWER SWITCH AIR INLET FILTER GAUZE...

Страница 9: ...TY JS 220308 004 9 Note The above mentioned product outlines and part names are only for one of the models and they will be slightly different in different models...

Страница 10: ...Requirements Cooling medium allowed by the chiller includes purified water distilled water high purity water and other softened water It is forbidden to use oily liquids liquids containing solid part...

Страница 11: ...ical connection 1 Please select the cable based on the max rated current indicated on the label of the chiller 2 Recommended reference standard for power cord diameter selection Rated current A 5 10 1...

Страница 12: ...eeting equipment cooling requirements The new T 504D intelligent temperature controller is designed with constant temperature control mode with water temperature maintained at 25 Users can adjust it a...

Страница 13: ...alarm display remains until the alarm condition is eliminated 5 General settings adjustment Press SET button SET to enter the user defined state Meanwhile D1 flashes and indicates that the controller...

Страница 14: ...to 26 5 if the air temperature is up to 30 5 water temperature will be between 28 0 to 27 0 Case 2 The cooling water temperature is controlled by the constant mode It is required that the water temper...

Страница 15: ...larm output port is connected with a set of normally open or normally closed contactsof the relay inside the machine The working current is required to be less than 3A while the working voltage is les...

Страница 16: ...is not triggered Water circulation pipes are blocked or a pipe is bent or deformed Check the water circulation pipe Ultra high temperature alarm Blocked dust gauze bad thermolysis Disassemble and clea...

Страница 17: ...Shengshi Industrial Zone Zhongcun Town Panyu District Guangzhou Sales Company Shanghai Top Nine Industrial Co Ltd Seller s Company Address No 208 Wulian Road Room164 Shanghai Pudong New District China...

Отзывы: