Installing the Refrigerant Pipe Work (Continued)
Insulation
Gas pipe
Liquid
pipe
Insulation
Gas pipe
10mm
Liquid pipe
10mm
10mm
Selecting the Insulation of the Refrigerant Pipe
According to pipes size ,Insulate pipes on gas and liquid side by selecting appropriate insulations.
The thickness standard is determined by the indoor temperature of 27°C and humidity of 80%.
If the units are in extreme conditions, use thicker one.
Pipe size (mm)
Minimum thickness
of insulation (mm)
Remarks
PE foam
EPDM foam
ø6.35~ø19.05
13
10
If you install the pipe underground, at the seaside,
a spa or on the lake, use thicker one according to the pipe size.
ø22.23
19
13
-
25
19
Refrigerant pipe before EEV kit or without EEV kit
The pipe work can be touching but not crushing the insulation.
When the pipes are touching, use thicker insulation.
Refrigerant pipe after EEV kit
Keep a 10mm separation of pipes after the EEV.
In case of small gap between gas and liquid pipe, use thicker
insulation .
Install the insulation not to be get wider and use the adhesives
on the connection part of it to prevent moisture entering.
Wind the refrigerant pipe with insulation tape if it is exposed
to outside sunlight.
Install the refrigerant pipe respecting that the insulation does
not get thinner on the bent part or hanger of pipe.