E-
18
Installing the Refrigerant Pipe Work (Continued)
Selecting the Refrigerant Pipe
Installing pipes between outdoor unit and first Y-joint
Outdoor unit
capacity (kW)
Liquid side
(mm)
Gas side (mm) Gas side size
up (mm)
RD060PHXEA
ø9.52
ø15.88
ø19.05
RD070PHXEA
ø9.52
ø15.88
ø19.05
RD080PHXEA
ø9.52
ø15.88
ø19.05
RD110PHXEA
ø9.52
ø15.88
ø19.05
RD140PHXEA
ø9.52
ø15.88
ø19.05
RD160PHXEA
ø9.52
ø15.88
ø19.05
Install refrigerant pipe depending on the outdoor unit
capacity.
Use the copper pipe of semi-hard(1/2H) when installing
Ø19.05 of the pipe.
If you use Soft(O) pipe, the internal pressure is too low to
cause personal injury.
Installing pipes between Y-joints
Indoor unit total
capacity (kW)
Liquid side (mm)
Gas side (mm)
X < 20.2
ø9.52
ø15.88
Outer
diameter
(mm)
Minimum
thickness
(mm)
Temper grade
ø 6.35
0.8
C1220T-O
(soft drawn)
ø 9.52
0.8
ø12.70
0.8
ø15.88
1.0
ø19.05
1.0
C1220T-1/2H
(hard drawn)
ø22.23
1.0
Temper grade and minimum thickness of
the refrigerant pipe