Locating the Units (Continued)
Installing the Outdoor Unit
Install the outdoor unit higher than 150mm from the base
surface and install the drain hole to connect the pipe to the
drainage.
If front fan outdoor unit is installed where average snow
fall is 150mm or more, a duct should be fitted to the unit.
The concrete foundation should be 1.5 times larger than
bottom of the outdoor unit.
When heating, condensed water may be generated.
Pay attention to waterproof and drainage of the
concrete foundation where the outdoor unit is installed.
(An ice patch may form on the base surface in winter.)
Install a square pad(t=20mm or more) to prevent vibration
of the outdoor unit delivering to the base surface when
installing the concrete for the outdoor unit.
Place the outdoor unit on the H beam and fix it with the bolt, nut and washer.
Do not install the outdoor unit on a wooden pallet palette.
Fix the outdoor unit completely to the base fix the outdoor unit with anchor bolts.
The manufacturer is not responsible for the damage occurred by not
keeping standard of the installation.
< When installing on the ground >
Drain hole
150 or more
< When installing on the roof >
Install the outdoor unit
horizontally on
the ground
150 or more
Base mount construction
(Unit : mm)
Outdoor unit
Anchor bolt
Nut, Spring
washer
H beam
Square pad
A+10~20mm or more
A
20mm
75mm