3-1
Chapter 3 Grounding, Power Connections
and
Cabling
Grounding
An equipment grounding conductor that complies with the electrical specifications of your country is to
be installed as part of the circuit that supplies the system. Bare, covered, or insulated grounding con-
ductors are acceptable. Individually covered or insulated equipment grounding conductors should
have a continuous outer finish that is either green or green with one or more yellow stripes.
The AC power outlets to which the system is to be connected should all to be of a grounding type. The
equipment grounding conductors serving these outlets should be connected to earth ground at the
service equipment.
WARNING: HIGH LEAKAGE CURRENT! Earth connection is essential before connecting
supply.
The system requires that a supplementary earth ground be connected. This is the preferred method of
grounding. The third-wire ground may be inferior or can contain noise that may prevent the digital data
bus from cancelling out noise, and may result in erratic operation. Also, some UPS battery systems do
not pass the ground through to the power cord, resulting in no ground to the system. The grounding
bar on the bottom of the left side of the cabinet must be connected to one of the following: bonded
building steel, cold water pipe or a ground rod using at least #16 AWG (1.3mm) copper wire. Addition-
ally, the ground between cabinets in a multiple cabinet system must also be at least #16 AWG
(1.3mm) copper wire. The third wire AC ground (or FG) is connected to the system frame via the
ground strap from the ground connector on the AC socket (
A supplementary equipment grounding conductor must be installed between the system and ground in
addition to the equipment grounding conductor in the power supply cord. The supplementary equip-
ment grounding conductor must not be smaller than the ungrounded branch-circuit supply conductors.
The supplementary equipment grounding conductor must be connected to the system at the terminal
provided, and must be connected to ground in a manner that will retain the ground connection when
the system is unplugged from the AC outlet
.
Termination of the supplementary equipment grounding
conductor may be made to building steel, to a metal electrical raceway system, or to any grounded
item that is permanently and reliably connected to the electrical service equipment ground.
Failure to provide an adequate ground may cause a safety hazard, faults or even circuit card
failure.
WARNING:
Unplug the power cord from the AC outlet before attempting to connect the
ground. Hazardous voltage may cause death or injury. Observe extreme caution when
working with AC power. Remove champ connectors from trunk cards.
Содержание OfficeServ500
Страница 1: ...SAMSUNG OfficeServ Installation Guide EnterpriseIPSolutions ...
Страница 11: ...502mm 567mm 300mm 1506mm 1004mm FIGURE 1 1 OFFICESERV500 CABINET DIMENSIONS 1 2 Chapter 1 Site Requirements ...
Страница 16: ...FIGURES 2 1 TO 2 4 ...
Страница 18: ...MOUNTING SCREWS FRONT LEFT SIDE BOTTOM FIGURE 2 2 ATTACHING LEGS TO MAIN CABINET ...
Страница 19: ...Bracket Bracket Screws Bracket Bracket Screws Ground Bar FIGURE 2 3 SIDE COVER MOUNTING BRACKETS ...
Страница 20: ...Mounting Screw Holes Mounting Screw Holes FIGURE 2 4 SECURING CABINET IN RACK ...
Страница 25: ...FIGURES 3 1 TO 3 4 ...
Страница 27: ...FIGURE 2 4 Power Input Location FIGURE 3 2 POWER INPUT LOCATION ...
Страница 28: ...110 220V selection switch FIGURE 3 3 SETTING VOLTAGE ON PSU ...
Страница 43: ...FIGURES 4 1 TO 4 24 ...
Страница 48: ...P1 P3 U7 U4 U6 U11 U3 P2 U2 U8 U5 U9 U10 U11 FIGURE 4 5 ESM BOARD ...
Страница 49: ...Screw Locations FIGURE 4 6 MCP2 LCP2 CARD SCREW LOCATIONS ...
Страница 50: ...P1 P2 P3 P4 U1 U2 U4 U4 U13 D3 D4 D2 D1 K2 K1 K3 T3 T4 T2 T1 FIGURE 4 7 MISC BOARD ...
Страница 51: ...Screw Locations FIGURE 4 8 SCP2 CARD SCREW LOCATIONS ...
Страница 52: ...P1 U7 U4 U5 P2 U2 U1 U6 U3 U8 FIGURE 4 9 SCM BOARD ...
Страница 53: ...P1 U7 U4 U5 P2 U2 U1 U6 U3 FIGURE 4 10 MFM BOARD ...
Страница 54: ...P2 U3 U4 P1 U1 U8 U5 U9 U2 FIGURE 4 11 RCM BOARD ...
Страница 55: ...U10 U9 U8 U5 U7 L1 L2 P1 P2 FIGURE 4 12 MODEM BOARD ...
Страница 60: ...EJECTOR TABS SCREWS FIGURE 4 17 TEPRI CARD SCREW LOCATIONS ...
Страница 64: ...FIGURE 4 21 SVMi 16 CARD SERIAL PORT RESET BUTTON VOICE PROCESSING MODULE DISK DRIVE ...
Страница 67: ...RAM ROM ROM ROM ROM RAM Clear J2 1F DSP JP1 A law u law FIGURE 4 24 VDIAL CARD ...
Страница 71: ...110 FUSES VOLTAGE SETTING FIGURE 5 1 FUSES ON PSU ...
Страница 74: ...FIGURES 6 1 TO 6 6 ...
Страница 75: ...FIGURE 6 1 MDF CONNECTIONS LOOP START LINE TO TRUNK B CARD ...
Страница 77: ...FIGURE 6 3 MDF CONNECTIONS AC15 CARD ...
Страница 78: ...FIGURE 6 4 MDF CONNECTIONS OFF PREMISES EXTENSION FROM SLI CARD ...
Страница 86: ...FIGURES 7 1 TO 7 8 ...
Страница 87: ...FIGURE 7 1a MDF CONNECTIONS DIGITAL KEYSET TO DLI CARD ...
Страница 88: ...FIGURE 7 1b MDF CONNECTIONS DIGITAL KEYSET TO 16DLI CARD ...
Страница 89: ...IP Phone LAN Ethernet OfficeServ500 Digital Phone MCP2 MGI2 3 16DLI FIGURE 7 2 IP PHONE CONNECTION ...
Страница 91: ...FIGURE 7 4 WALL MOUNTING A DCS EURO KEYSET ...
Страница 92: ...1 2 1 3 FIGURE 7 5 WALL MOUNTING AN iDCS SERIES KEYSET WITH BASE WEDGE ...
Страница 93: ...FIGURE 7 6a MDF CONNECTIONS ADD ON MODULE TO DLI CARD ...
Страница 94: ...FIGURE 7 6b MDF CONNECTIONS ADD ON MODULE TO 16DLI CARD ...
Страница 95: ...FIGURE 7 7a MDF CONNECTIONS SINGLE LINE TELEPHONE TO SLI CARD ...
Страница 96: ...FIGURE 7 7b MDF CONNECTIONS SINGLE LINE TELEPHONE TO 8SLI OR 8MWSLI CARD ...
Страница 97: ...FIGURE 7 7c MDF CONNECTIONS SINGLE LINE TELEPHONE TO 16SLI CARD ...
Страница 98: ...FIGURE 7 7d MDF CONNECTIONS SINGLE LINE TELEPHONE TO 16MWSLI CARD ...
Страница 99: ...FIGURE 7 8a MDF CONNECTIONS DOOR PHONE AND DPIM TO DLI CARD ...
Страница 100: ...FIGURE 7 8b MDF CONNECTIONS DOOR PHONE AND DPIM TO 16DLI CARD ...
Страница 104: ...FIGURES 8 1 TO 8 6 ...
Страница 115: ...FIGURES 9 1 TO 9 2 ...
Страница 117: ...FIGURE 9 2 CONNECTING iDCS 28D AND 18D KEYSET DAUGHTERBOARDS ...
Страница 132: ...Samsung Telecoms U K Limited Brookside Business Park Greengate Middleton Manchester M24 1GS ...