40
Field setting mode
English
Fiel
d S
etting Mode
Main
Menu &
Code
Menu
Function
Sub
Code
MODEL CODE :
AE200 (260)RNW***
MODEL CODE :
MIM-E03CN
Setting Standard
Setting Standard
Item
Step Unit
Default Min. Max. Default Min. Max.
Others
Code
50**
Additional
Function
PV
Control
Application
1
-
ߦߡߩߢ
0 (No)
0
1
(Yes)
0 (No)
0
1
(Yes)
Setting Temp Shift
Value (Cooling)
1
ઑA
ߦߡߩߣ
2
1
20
2
1
20
Setting Temp Shift
Value (Heating)
1
ઑA
ߦߡߩߤ
2
1
50
2
1
50
Smart
Grid
Control
Application
1
-
5091 0 (No)
0
1
(Yes)
N/A
N/A N/A
Setting Temp Shift
Value (Heating)
1
ઑA
5092
2
1
50
N/A
N/A N/A
Setting Temp Shift
Value (DHW)
1
ઑA
5093
5
1
40
N/A
N/A N/A
DHW Mode
( (Target Tank Temp.)
1
-
5094
0
0
1
N/A
N/A N/A
Others : Code 50**
Outing Mode
࡙
All the target temperatures – space heating and cooling, water law, DHW, Room temperature – are set
to the values defined in the above table under the holiday mode.
NOTE
࡙
With the lowered target temperatures (FSV #5011 ~ #5019), the system operates normally.
Economic DHW Heating
࡙
DHW heating only by the heat pump to save energy (Operated in Eco mode of wired remote control)
Target DHW temperature is lower than the temperature set by user.
The temperature difference is defined by FSV #5021. (default: 5°C) If user sets the temperature 45°C,
the system sets the target temperature 40°C with the default setting.
ࣕ
If user want additional energy saving, use a “Saving mode” (#5022, default : 0, OFF)
ࣕ
The user can set the “Thermo On” temperature during “Saving mode” using FSV #5023