Control Systems
34
I
I
Individual control systems
F1/F2
F3/F4
Group control (3)
Control 1 or multiple indoor units with 2 wired remote controllers
Control
All connected indoor units
Display
Priority 1. Display the status of view master indoor unit
Priority 2. Display the status of indoor unit which has the earliest Main address
Ï
5XPXJSFESFNPUFDPOUSPMMFSTJEFOUJDBMMZEJTQMBZUIFPQFSBUJPOTUBUVTPGUIFJOEPPSVOJU
according to above priority.
Wired remote controller
Indoor unit
Outdoor unit
Master
Master
Slave
Slave
F1/F2
F3/F4
Indoor unit
Group control (4)
Control multiple indoor units connected to different outdoor units with 2 wired remote controller
Control
All connected indoor units
Display
Priority 1. Display the status of view master indoor unit
Priority 2. Display the status of indoor unit which has the earliest Main address
Ï
5XPXJSFESFNPUFDPOUSPMMFSTJEFOUJDBMMZEJTQMBZUIFPQFSBUJPOTUBUVTPGUIFJOEPPSVOJU
according to above priority.
Wired remote controller
Master Slave
Outdoor unit
Outdoor unit
Ú
Maximum 16 indoor units can be connected
Ú
Maximum 16 indoor units can be connected
100m
Max. distance between the farthest indoor unit and wired
remote controller : 100m
Wired remote controller
3. Wired remote controller
$PNNVOJDBUJPOEJBHSBN
MWR-SH00N
f
Caution
When controlling group of indoor units connected to different outdoor unit, address of the each outdoor unit must be set differently.
Содержание MR-DH00
Страница 8: ...DVM CONTROL SYSTEMS 8...
Страница 75: ...75 III Integratedmanagementsystems DMS2 S NET3 76 111 1 2 I NTEGRATED M ANAGEMENT S YSTEMS...
Страница 93: ...I NTEGRATED M ANAGEMENT S YSTEMS 93 MJDL MJDL QQMJDBUJPO DPNQMFUFE Register control logic Control logic applied...
Страница 127: ...127 MFDUSJDJUZ NFUFS JOUFSGBDF NPEVMF 128 1 IV Powerdistributionsystem P OWER D ISTRIBUTION S YSTEM...
Страница 184: ...DVM CONTROL SYSTEMS 184 Uw G G U GGGX_ YWX TW TY GGG G aZ a...
Страница 197: ...197 MEMO Uw G G U GGGX YWX TW TY GGG G aZ a...