169
B
UILDING
M
ANAGEMENT
S
YSTEM
(3) ERV
Instance
Number
Object
Object
Type
Object Name
Unit
Status value
Inactive
Active
Text-1
Text-2
Text-3
Text-4
Text-5
1
Power On/Off operation
BV
&37@1PXFS@YY@YYYYYY
Off
On
2
Filter sign status
BI
ERV_FilterSign_xx_xxxxxx
False
True
3
Filter sign reset
BO
ERV_FilterSign_Reset_xx_xxxxxx
False
True
4
Operation mode status
MV
ERV_Operation_Mode_xx_xxxxxx
Auto
HeatEx
Bypass
Sleep
5
Fan speed status
MV
ERV_FanSpeed_xx_xxxxxx
Low
High
Turbo
6
Remote controller limit status
MV
ERV_Remocon_Limit_xx_xxxxxx
Enable
RC
Disable
RC
Conditional
RC
7
Integrated error code of ERV
unit
AI
ERV_Error_Code_xx_xxxxxx
Refer to list of error code
8
ERV Notify
NC
ERV_Notify_xx_xxxxxx
When the error occurred, send event to list
of destination in the recipient_list. (Max : 8)
Single ERV unit has following point list.