Samsung MIM-B16 Скачать руководство пользователя страница 8

E-

8

PIM System Architecture

 

Maximum 8 PIM units can be connected to DMS or DMS2.

Maximum 8 watt-hour meters can be connected to PIM.

R2 R1 R2 R1

R1 R2

R2 R1 R2 R1

R1 R2

R2 R1 R2 R1

R1 R2

R2 R1 R2 R1

R1 R2

DMS or DMS2

Centralized 

controller

PIM

Watt-hour 

meter

Watt-hour meter 

(max. 8 units)

Interface 

module 

ROOM 0

ROOM 1

ROOM 2

Outdoor Unit

Pulse input

MIM-B16_PIM_IM_E 32320-1.indd   8

2010-05-20   ソタネト 7:18:46

Содержание MIM-B16

Страница 1: ...INSTALLATION MANUAL MIM B16 DB98 32320A 1 E PIM Pulse Input Module MIM B16_PIM_IM_E 32320 1 indd 33 2010 05 20 ソタネト 7 19 08 ...

Страница 2: ...WARNING CAUTION Do not use inflammable gases near the PIM Do not install the PIM in a location where it will come into contact with combustible gases machine oil sulphide gas etc Avoid locations where acid alkali solution or special spray is used Choose a location that is dry and sunny but not exposed to direct sunlight Suitable temperature is between 0 C 32 F and 39 C 102 2 F Do not spill water i...

Страница 3: ...FETY PRECAUTIONS 2 ACCESSORIES 4 VIEWING THE PARTS 5 PRODUCT DIMENSIONS 7 PIMSYSTEM ARCHITECTURE 8 INSTALLING THE PIM 9 SETTING THE PIM 16 PIMMENU DESCRIPTION 17 MIM B16_PIM_IM_E 32320 1 indd 3 2010 05 20 ソタネト 7 18 42 ...

Страница 4: ...PIM must be installed by a trained installer Ensure the main power is turned off before installing the PIM Be sure to use adapter and power cable we provide The power cable and the communication cable must be installed according to the national electrical wiring regulations Use 2C x 0 75mm2 communication cable Item PIM Quantity 1 Shape MIM B16_PIM_IM_E 32320 1 indd 4 2010 05 20 ソタネト 7 18 43 ...

Страница 5: ...he bottom cover from PIM Then check cable connection part Item Name Status Power Power indicator Turns blue when the power is supplied COM1 TX RX Data transmission reception with DMS indicator Blinks in orange during the normal transmission reception Signal 1 8 Power consumption pulse input indicator Blinks in orange when the normal pulse is input from the watt hour meter COM2 TX RX Reserved Reser...

Страница 6: ...Communication terminal COM1 Connection terminal for RS485 communication with DMS or DMS2 COM2 Reserved Cable tie groove Groove for arranging cables Viewing the Parts Continued PIM Cable Connection Part Cable tie groove Power terminal Reset button Pulse input terminal Channel 1 4 RS485 communication terminal COM1 COM2 Pulse input terminal Channel 5 8 Main Parts MIM B16_PIM_IM_E 32320 1 indd 6 2010 ...

Страница 7: ...E 7 240 255 64 80 Unit mm Display board 40 pin cable 20 pin cable Main board Sub board PIM Interior Product Dimensions MIM B16_PIM_IM_E 32320 1 indd 7 2010 05 20 ソタネト 7 18 45 ...

Страница 8: ...eters can be connected to PIM R2 R1 R2 R1 R1 R2 R2 R1 R2 R1 R1 R2 R2 R1 R2 R1 R1 R2 R2 R1 R2 R1 R1 R2 DMS or DMS2 Centralized controller PIM Watt hour meter Watt hour meter max 8 units Interface module ROOM 0 ROOM 1 ROOM 2 Outdoor Unit Pulse input MIM B16_PIM_IM_E 32320 1 indd 8 2010 05 20 ソタネト 7 18 46 ...

Страница 9: ...er and fix the installation plate and PIM using 2 screws Depending on the installation environment open the top cover and fix PIM using assistant holes Screws for assistant hole are not provided 5 If you install PIM inside of the wall or wiring from the rear side is needed use wiring groove on the bottom of PIM Installing the PIM on theWall TopreventbreakdownanddamageofPIMandforsafeusage itisrecom...

Страница 10: ... 8 terminal blocks which are attached to the pulse input terminal of PIM For the communication cable connection instruction of watt hour meter or additional setting instruction refer to the installation manual of watt hour meter Connect the communication cable considering the polarity Left Right Maximum8watt hourmeterscanbeconnectedto1PIM Use2Cx0 75mm2 communicationcable Adapter Connecting Watt Ho...

Страница 11: ...e Watt hour meter with Separate External Output Connect according to the pulse output specification Watt hour meter whose Pulse Output Error is less than 5 e g When the pulse width is 100ms you can use the watt hour meter whose pulse width is within 95 105ms Watt hour meter must have more than 3ms Delay Between the First Pulse Input and the Next Pulse Open More than 3ms Mandatory Open Short Short ...

Страница 12: ...tion about the polarity when connecting RS485 communication A of PIM of DMS B of PIM B of DMS 2 Close the bottom cover and fix it using 2 screws Connecting PIM to DMS or DMS2 Connect communication cable Connect communication cable Connect communication cable PIM DMS DMS2 A B A B A B MIM B16_PIM_IM_E 32320 1 indd 12 2010 05 20 ソタネト 7 18 49 ...

Страница 13: ...user manual page 30 When execute tracking with PIM which connected to DMS2 ver 2 1 2 or later version For the further information about tracking refer to the DMS2 user manual page 121 Displays the number of SIM which included the number of connected PIM Displays the number of SIM or PIM A name of a PIM MIM B16_PIM_IM_E 32320 1 indd 13 2010 05 20 ソタネト 7 18 50 ...

Страница 14: ...E 14 Installing the PIM Continued If PIM is connected to DMS2 ver 2 1 2 or later version PIM setting through DMS2 web is possible MIM B16_PIM_IM_E 32320 1 indd 14 2010 05 20 ソタネト 7 18 50 ...

Страница 15: ... 6 16H 7 17H 8 F Not used 3 Close the top PIM cover and fix it using 2 screws Installing more than 2 PIM Units to 1 DMS Error Codes Display Explanation E613 DMS PIM communication error if communication is not working over 3 minutes E632 Error occurs when improper pulses which are not in the range of limitation are input over 15 times continuously Error occurs when High pulses are input for over 3 ...

Страница 16: ... 2 4 PIM Time For the further information refer to page 24 25 The display above is an example 2 Configuration 2 2 Wh Pulse Set CH1 Wh P CH1 00001Wh P Setting for the Connected Watt hour meter Setting the pulse constant of watt hour meter Main menu 2 Configuration 2 2 Wh Pulse For the further information refer to page 22 2 Configuration 2 3 Pulse Width Set CH1 P Width CH1 20ms Setting the pulse wid...

Страница 17: ... 3 Check 2 Configuration 2 1 Password 2 2 Wh Pulse 2 3 Pulse Width 2 4 PIM Time 2 5 Channel 2 6 KWh Set 2 7 KWh Clear 3 1 Pulse Input 3 2 COM Check 3 3 Pulse Width CH1 00000 0kWh CH2 00000 0kWh CH8 00000 0kWh Normal Display Displayed repeatedly MIM B16_PIM_IM_E 32320 1 indd 17 2010 05 20 ソタネト 7 18 52 ...

Страница 18: ...t is subject to change according to the setting 2 Power consumption of pulse input CH1 CH8 will be displayed in order 3 Current time will be displayed after the power consumption of CH8 It displays CH1 CH8 and current time repeatedly You can make the display stop moving with using Set button for easy view You can find which channel you want to see with using the buttons PIM Menu Description Contin...

Страница 19: ...l the setting All menus will return to the normal display if there is no input for 1 minute PIM Address 1 Monitoring 1 2 Option S W 1 2 Option S W 12345X78 1 Access to main menu by pressing the Menu button from the normal display Then select 1 Monitoring by pressing the Set button 2 Move to 1 2 Option S W menu by pressing the buttons then select it by pressing the Set button Note Example display 1...

Страница 20: ...tion menu Setting the Password 2 Configuration 2 1 Password 3 Select 2 1 Password by pressing the Set button 2 1 Password Password Set 4 Select Password Set by pressing the Set button to set the new password Set your P W 5 Set the new password using the buttons and press the Set button Save Settings 0 0 0 0 6 Press the Set button to save the setting 7 After the setting press the Menu button to mov...

Страница 21: ...ing the Set button 2 1 Password Password Reset 4 Select Password Reset by pressing the Set button to reset the password Password Reset 5 Press the Set button to reset the password To cancel resetting press the Menu button If you press the Set button the password will reset to 0000 6 After the setting press the Menu button to move to upper menu or cancel the setting All menus will return to the nor...

Страница 22: ...he channel you want to set by pressing the buttons and then press the Set button You can select each channel or all channel altogether 5 Modify the digit by pressing the buttons You can move to the next digit by pressing the Set button Default 1Wh Pulse Range 1Wh Pulse 10 000Wh Pulse If you set Wh Pulse from ALL all Wh Pulse will be changed at the same time 6 Press the Set button to save the setti...

Страница 23: ...ove to the channel you want to set by pressing the buttons and then press the Set button You can select each channel or all channel altogether 5 Modify the digit by pressing the buttons You can move to the next digit by pressing the Set button Default 20ms Range 20ms 400ms If you set pulse width from ALL all pulse width will be changed at the same time 6 Press the Set button to save the setting 7 ...

Страница 24: ...ng the Set button Current Date 2010 01 05 5 Previously set date will be displayed Press the Set button to set the current date Y M D Press the Menu button to return to the upper menu Set Current Date 2010 01 05 6 Modify the date in order of year month and day by pressing the buttons You can move to the next item by pressing the Set button Date setting 7 Press the Set button to save the setting Pre...

Страница 25: ...tton Current Time 11 25 14 PM 5 Previously set time will be displayed Press the Set button to set the current time H M S Press the Menu button to return to the upper menu Time setting 7 Press the Set button to save the setting Press the Menu button to return to the upper menu 8 After the setting press the Menu button to move to upper menu or cancel the setting All menus will return to the normal d...

Страница 26: ...o set by pressing the buttons and then press the Set button You can select each channel or all channel altogether 2 5 Channel Channel1 En 5 Enable Press the Set button when Enable Channel appears Disable Press the buttons and then press Set button when Disable Channel appears To enable disable all channels select ALL in step 4 Disabled channel will not be displayed on the normal display 6 After th...

Страница 27: ...xt digit by pressing the Set button You can reset the current power consumption by entering the initial value of the watt hour meter which connected to the channel Reset power consumption Entered watt hour meter value Wh Pulse When resetting the initial value of watt hour meter it clears the pulse and power consumption which input so far It will calculate the power consumption based on the changed...

Страница 28: ...essing the buttons and then press the Set button You can select each channel or all channel altogether 2 7 kWh Clear CH1 00000 0kWh 5 Press the Set button to initialize the selected channel when the caution message appears Clear Initializes the power consumption calculated so far To cancel the initialization press the Menu button To initialize all channels you can select ALL Channel in step 4 6 Pr...

Страница 29: ...yed when there is no input within 10 seconds after selecting the channel If the pulse input is normal Displayed in number If there is no pulse input Displayed X CH1 3 4 6 8 No pulse input CH2 5 7 OK PIM does not calculate the power consumption during the inspection Calculation will start after the inspection and returning to the upper menu To check the status of all channels select All Check OK in...

Страница 30: ...t transmission reception status with DMS COM Check End OK 3 Communication inspection result will be displayed OK NG 4 After the inspection press the Menu button to move to upper menu or cancel the setting All menus will return to the normal display if there is no input for 1 minute 3 Check 3 2 COM Check COM Check Start Checking You can check if the RS485 circuit is normal when you have doubt the m...

Страница 31: ...ting measurement OK If the setting and measurement are same NG If the setting and measurement are not same However if there is no pulse input within 10 seconds after selecting channel it will show NG PIM does not calculate the power consumption during the checking process Calculation will start after the check and returning to the upper menu 5 After the checking press the Menu button to move to up...

Страница 32: ...MIM B16_PIM_IM_E 32320 1 indd 32 2010 05 20 ソタネト 7 19 08 ...

Отзывы: