E-
10
Installing the PIM (Continued)
1
Unfasten the 2 screws on the bottom of the PIM front
cover. Hold the bottom 2 sides of the PIM and push
downwards to slide open the cover.
2
Connect the adapter to the power terminal.
Arrange the adapter as shown in the figure.
3
Connect PIM and watt-hour meter as many as you want.
In this step, use communication cable and 8 terminal
blocks which are attached to the pulse input terminal
of PIM.
For the communication cable connection instruction of
watt-hour meter or additional setting instruction, refer
to the installation manual of watt-hour meter.
Connect the communication cable considering the
polarity. [Left:(+), Right:(-)]
Maximum 8 watt-hour meters can be connected to 1 PIM.
Use 2Cx0.75mm
2
communication cable.
Adapter
Connecting Watt-Hour meter and PIM
Connecting Watt-hour meter, PIM and DMS
Connect
communication
cable
Watt-hour meter
(+) (-)
MIM-B16_PIM_IM_E 32320-1.indd 10