E-
15
1
Unfasten the 2 screws on the top of the PIM. Hold the top
2 sides of the PIM and pull it the cover upwards to open
the cover.
2
Set the PIM address using rotary switch of main PCB.
(Default setting: 10H)
Switch 1: Not used
Switch 2
Switch setting
Address
0
10H
1
11H
2
12H
3
13H
4
14H
5
15H
6
16H
7
17H
8~F
Not used
3
Close the top PIM cover and fix it using 2 screws.
Installing the PIM (Continued)
Installing more than 2 PIM Units to 1 DMS
Error Codes
Display
Explanation
E613
DMS
PIM communication error if communication
is not working over 3 minutes
E632
- Error occurs when improper pulses which are not
in the range of limitation are input over 15 times
continuously.
- Error occurs when High pulses are input for over
3 minutes.
E654
FRAM Read/Write error