Deciding on Where to Install the Air Conditioner (Continued)
P
REPARING THE
I
NSTALLATION
E-
6
◆
MH050FXEA2B
❊
MH050FXEA2B cannot be connected to the following indoor unit combination. - MH052FMEA
300 mm
minimum
600 mm
minimum
600 mm
minimum
300 mm
minimum
Main power switch
(h)
(H)
A
B
◗
Piping length and the height
Dimension
Composition
1 Room max
length
20 m
A, B
2 Room total max
length
30 m
A + B
Max height between
indoor unit & outdoor unit
15 m
(H)
Max height between
indoor units
7.5 m
(h)
Make at least one round :
It will reduce noise and vibration.
◗
System can work with one indoor unit connected,but it is recommended that the TOTAL number of
indoor unit suggested by manufacturer are connected to obtain the maximum performance.
❊
The appearance of the unit may be different from the diagram depending on the model.
1, 220-240, 50
Indoor unit
Outdoor unit
Power supply
Ø, V, Hz
MH
✴✴✴
FKEA
MH
✴✴✴
FSEA
MH030FMEA
MH035FMEA
MH050FXEA2B
✴✴
026/030/035
✴✴
Liquid
1/4”
Gas
3/8”
Unit
Outside diameter
◗
Piping outside diameter
3m as minimum pipe length. It will reduce noise
and vibration.
If just one indoor unit is connected this value
must be increased up to 7.5m.