Indoor Unit Installation

It is recommended to install the refnet joint before installing the indoor unit.

4

Screw eight nuts to the suspension bolts making space for hanging
the indoor unit.

5

Check the level of the indoor unit by using a leveler or a vinyl tube filled
with water.

A tilt of the indoor unit may cause malfunction of a built-in float switch and
water leaks.

6

Adjust the height of the indoor unit by using the gauge of dimensions.

You should adjust the gauge of dimensions and the pattern sheet to fit
the cutting dimensions of ceiling.

Make sure that the indoor unit is installed at a level if the indoor unit
slants too much, there can be water leaks.

7

Tighten the upper part nuts.

8

Remove the gauge of dimensions after installing the indoor unit.

You must install the suspension bolts more than four
when installing the indoor unit.

C

C

C

C

A

A

A

A

U

U

U

U

T

T

T

T

II

II

O

O

O

O

N

N

N

N

Not supplied

Washer(supplied)

Rubber

Level

Vinyl tube

Fasten the nut

1

Place the pattern sheet on the ceiling at the spot where you want to
install the indoor unit.

2

Insert bolt anchors, use existing ceiling supports or construct a suitable
support as shown in figure.

3

Install the suspension bolts depending on the ceiling type.

Ensure that the ceiling is strong enough to support the
weight of the indoor unit. 
Before hanging the unit, test the strength of each
attached suspension bolt.

If the length of suspension bolt is more than 1.5m, it is
required to prevent vibration.

If this is not possible, create an opening on the false 
ceiling in order to be able to use it to perform the
required operations on the indoor unit.

C

C

C

C

A

A

A

A

U

U

U

U

T

T

T

T

II

II

O

O

O

O

N

N

N

N

Since the diagram is made of paper, it may shrink or stretch slightly
due to temperature or humidity. For this reason, before drilling the
holes maintain the correct dimensions between the markings; refer
to pages 11~13.

N

N

N

N

o

o

o

o

tt

tt

e

e

e

e

Concrete

Suspension bolt(3/8" or M10)

Hole in anchor
Hole in plug

Insert

Ceiling support

20mm

25mm

Gauge of Dimensions Ceiling

Air 
inlet

Air 

outlet

MH

✴✴✴

FKEA

15mm

15mm

Gauge of Dimensions Ceiling

Air 
inlet

Air 

outlet

MH

✴✴✴

FSEA

Gauge of
Dimensions

MH

✴✴✴

FMEA

17mm

20mm

Ceiling

Indoor Unit

 MH***FKEA IM_E_27682_4  5/25/04 3:28 AM  Page 14

Содержание MH FKEA Series

Страница 1: ...ANO PORTUGU S DEUTSCH E HNIKA RUSSIAN E S F I P D G R DB98 27682A 7 Cassette Type Series MH FKEA MH FSEA MH FMEA INSTALLATION MANUAL Free Joint Multi Air Conditioner Cooling and Heating MH FKEA IM_E_2...

Страница 2: ...contains a refrigerant that has to be disposed of as special waste At the end of its life cycle the air conditioner must be disposed of in authorized centers or returned to the retailer so that it can...

Страница 3: ...5 Connecting the Refrigerant Pipe 16 Cutting Flaring the Pipes 17 Performing Leak Test Insulation 18 Drainpipe and Drain Hose Installation 19 Connecting the Connection Cord 21 Wiring Wired Remote Cont...

Страница 4: ...bles to be easily connected to the outdoor unit and the recommended length of 7 5 metres to be respected Leave enough clearance beneath the indoor unit to enable the filters to be removed without hind...

Страница 5: ...nd the height System can work with one indoor unit connected but it is recommended that the TOTAL number of indoor unit suggested by manufacturer are connected to obtain the maximum performance Dimens...

Страница 6: ...reduce noise and vibration System can work with one indoor unit connected but it is recommended that the TOTAL number of indoor unit suggested by manufacturer are connected to obtain the maximum perf...

Страница 7: ...between indoor unit outdoor unit 15 m H Max height between indoor units 7 5 m h Make at least one round It will reduce noise and vibration System can work with one indoor unit connected but it is reco...

Страница 8: ...otal max length 70 m A B C D Max height between indoor unit outdoor unit 15 m H Max height between indoor units 7 5 m h Make at least one round It will reduce noise and vibration System can work with...

Страница 9: ...and Insulation Cable tie The following accessories are supplied with the indoor unit The type and quantity may differ depending on the specifications MH FKEA MH FSEA Pattern sheet Insulation cover ban...

Страница 10: ...d in this way that they are out of public access Not touchable by the users E 10 Space Requirements for Indoor Unit INSTALLING THE INDOOR UNIT MH FKEA MH FSEA MH FMEA The units must be installed accor...

Страница 11: ...9 52 3 8 OD 29 ID 25 No Name Description Net dimension Net weight Indoor unit Panel size Indoor unit Panel 970 x 180 x 390 1180 x 25 x 460 15 Dimension and weight Drawing of the indoor unit Unit mm MH...

Страница 12: ...uid pipe connection Gas pipe connection Drain pipe connection Power supply connection Air discharge grille Air suction grille 6 35 1 4 9 52 3 8 OD 29 ID 25 No Name Description Net dimension Net weight...

Страница 13: ...x 575 670 x 35 x 670 19 6 Dimension and weight 026 035 052 mm kg 1 2 3 4 5 6 Liquid pipe connection Gas pipe connection Drain pipe connection Power supply connection Air discharge grille Air suction g...

Страница 14: ...ng at the spot where you want to install the indoor unit 2 Insert bolt anchors use existing ceiling supports or construct a suitable support as shown in figure 3 Install the suspension bolts depending...

Страница 15: ...en gas insert gas Therefore all insert gas must be purged before connecting the assembly piping Make sure all the nitrogen gas is purged out before installing the unit If not do not install the unit b...

Страница 16: ...e e Outer Diameter Torque N m 6 35 mm 1 4 18 9 52 mm 3 8 42 12 70 mm 1 2 55 15 88 mm 5 8 65 19 05 mm 3 4 100 22 23 mm 7 8 100 Insulation refrigerant pipe Clamp Refrigerant oil Insulation refrigerant p...

Страница 17: ...ng 5 Align the pipes and tighten the flare nuts first manually and then with a torque wrench applying the following torque 6 Outer Diameter D Depth A 6 35 mm 1 4 1 3mm 9 52 mm 3 8 1 8mm 12 70 mm 1 2 2...

Страница 18: ...s the insulation too much 2 Finish wrapping insulating tape around the rest of the pipes leading to the outdoor unit 3 The pipes and electrical cables connecting the indoor unit with the outdoor unit...

Страница 19: ...r band Insulation cover drain Band Not supplied Indoor Unit Drainpipe MH FMEA MH FKEA MH FSEA Flexible hose If it is necessary to increase the height of the drainpipe install the drainpipe straightly...

Страница 20: ...ter supply intake 2 Operate the unit in the Cool mode and check a drain pump pumping 3 Check drain water drops at the end of the drainpipe 4 Make sure there is no water leak at the drainage 5 When you...

Страница 21: ...or a more power model with insulation in synthetic rubber and jacket in polychloroprene neoprene in accordance with the requirements of standard EN 60335 2 40 Remove the screw on the electrical compon...

Страница 22: ...4 terminal Wiring Wired Remote Control Optional F1 F2 V1 V2 1 L 2 L F1 F3 F2 F4 V1 V2 Indoor Unit Terminal Block Wired Remote Control Optional Accessory in the remote control Indoor Unit PCB CN32 BLU...

Страница 23: ...et the RMC address if you install the wired remote control and or the centralized control 4 If you install optional accessories such as the wired remote control centralized control etc see an appropri...

Страница 24: ...ion ON OFF SW06 K6 Filter time 1000 hours 2000 hours K5 Indoor Temperature Compensation for Heating Mode 2 C 5 C K7 K8 MH FSEA No Function ON OFF SW06 K6 Filter time 1000 hours 2000 hours K5 Indoor Te...

Страница 25: ...depending on the time during which the air conditioner is used Remove the vinyl packing from the filter 1 Bio pure filter Deodorizing filter Deodorizing filter 1 Bio pure filter 1 Accessories When ins...

Страница 26: ...pump models only Error of mixed operation Error of indoor fan motor Below 450RPM for 15 minutes Error of outdoor temperature sensor Error of COND sensor Error of DISCHARGE sensor 1 No communication f...

Страница 27: ...ed off Displayed on appropriate indoor unit which is operating Displayed on outdoor unit 1 2nd detection of refrigerant completely leak 2 2nd detection of high temperature COND 3 2nd detection of high...

Страница 28: ...Printed in Korea MH FKEA IM_E_27682_6 5 14 04 12 58 AM Page 4...

Отзывы: