ENGLISH-95
0
2
INST
ALLING
THE
PRODUC
T
K2 (Number of
press)
KEY operation
Display on segment
1
Refrigerant charging in Cooling mode
K - 5 - BLANK - BLANK
2
Trial operation in Cooling mode
K - 6 - BLANK - BLANK
3
Pump down all units in Cooling mode
K - 7 - BLANK - BLANK
4
HR: Pipe connection inspection
H/P: Auto trial operation
K - 8 - BLANK - BLANK
5
Checking the amount of refrigerant
K - 9 - X - X
(Display of last two digits may differ depending on
the status)
6
Discharge mode of DC link voltage
K - A - BLANK - BLANK
7
Forced oil collection
K - C - BLANK - BLANK
8
Inspect inverter compressor 1
K - D - BLANK - BLANK
9
Inspect inverter compressor 2
K - E - BLANK - BLANK
10
Water pipe valve/Pump check
K - F - BLANK - BLANK
11
Cooling fan/Flow control valve check
K - G - BLANK - BLANK
12
End key operation
-
❋
During “Discharge mode of DC link voltage”, voltage of INV1 and INV2 will be displayed alternately.
❋
Even when the outdoor unit power is off, it is dangerous when you come in contact with inverter PCB and fan PCB since
they are charged with high DC voltage.
❋
When there were error, ‘Discharge mode of DC link voltage’ may not have been effective. Especially if error E464 and E364
have been occurred, power element might be damaged by fire and therefore, do not use the ‘Discharge mode of DC link
voltage’.
K3 (Number of
press)
KEY operation
Display on segment
1 time
Initialize (Reset) setting
Same as initial state