ENGLISH-40
Refrigerant pipe installation
Pipe installation for an outdoor unit
1. The outdoor unit of AM
✴✴✴
KXWD is the non-modular H/P exclusive system.
2. The outdoor unit of AM
✴✴✴
HXWA is used for both modular H/P and HR systems. Connect the liquid and gas pipes to
the outdoor unit as shown in the figure.
- For H/P System, connect liquid and gas pipes to an indoor unit.
- For HR System, connect liquid and high/low pressure gas pipes to a MCU. Close the internal heat pump valve and set
the K5 switch to ‘OFF’.
- For module installation, make sure that each heat pump valve and K5 switch setting is adjusted according to each
purpose. (When installing outdoor units in module, E573 error may occur when settings are different between outdoor
units.)
Classification
H/P system
HR system
AM038/048/055KXWD
✴
AM072/096/120/192HXWA
✴
Service
valve
Liquid
pipe (high
pressure)
Gas pipe
(low
pressure)
Liquid pipe
High
pressure
gas pipe
Not in use
(Low
pressure
gas pipe)
Heat pump
valve
(Open)
Liquid pipe
High
pressure
gas pipe
Low
pressure
gas pipe
Heat
pump
valve
(Close)
Heat pump
valve
-
Open (Factory default)
Close (Set during installation)
Option
switch (K5)
-
ON (Factory default)
OFF (Set during installation)