ENGLISH-86
Setting outdoor unit option switch and key function
K3 (Number of press)
KEY operation
Display on 7-Segment
1 time
Initialize (Reset) operation
Same as initial state
View Mode
Table. View mode 1
K4 (Number of press)
Display content
Display
SEG 1
SEG 2,3,4
1 time
Outdoor Capacity
1
16 horsepower
ĺ
0,1,6
2 times
Target frequency (Compressor)
2
120Hz
ĺ
1,2,0
3 times
High pressure (kg/cm2)
3
15.2K
ĺ
1.5.2
4 times
Low pressure (kg/cm2)
(Value of 1 second)
4
4.3K
ĺ
0.4.3
5 times
Discharge temperature
(Compressor)
5
87 °C
ĺ
0.8.7
6 times
IPM temperature (Compressor)
6
87 °C
ĺ
0.8.7
7 times
CT sensor value (Compressor)
7
2 A
ĺ
0.2.0
8 times
Suction temperature
8
-42 °C
ĺ
-.4.2
9 times
COND OUT temperature
9
-42 °C
ĺ
-.4.2
10 times
Temperature of liquid pipe
A
87 °C
ĺ
0.8.7
11 times
TOP temperature (Compressor)
B
87 °C
ĺ
0.8.7
12 times
Water temperature
C
-42 °C
ĺ
-.4.2
13 times
Main EEV step
D
2000
ĺ
2.0.0
14 times
ESC EEV step
E
300
ĺ
3.0.0
15 times
Current frequency of the
compressor
F
120Hz
ĺ
1.2.0
16 times
Address of master indoor unit
G
When master indoor unit is not set
ĺ
BLANK, N, D
When indoor unit No.1 is set as master
indoor unit
ĺ
0.0.1
17 times
Temperature of control box
H
-42 °C
ĺ
-.4.2
Press K4 for 3 seconds to use View mode 2
Table. View mode2
K4 (Number of press)
Display content
Display
Page 1
Page 2
1 time
Main version
MAIN
Version (Example: 1412)
2 times
Water hub version
HUB2
Version (Example: 1412)
3 times
Inverter 1 version
INV1
Version (Example: 1412)
4 times
EEP version
EEP
Version (Example: 1412)
5 times
Received units
AUTO
SEG1, 2
SEG3, 4
Automatically assigned
address
Indoor unit: “A”, ”0”
Address
(Example: 07)
MCU : “C”,”1”
6 times
Received units
MANU
SEG1, 2
SEG3, 4
Manually assigned
address of the units
Indoor unit: “A”, ”0”
Address
(Example: 15)