ENGLISH-55
0
2
INST
ALLING
THE
PRODUC
T
Installing the MCU
MCU specification
Model
MCU-S6NEE1N
MCU-S4NEE1N
MCU-S4NEE2N
Exterior of MCU
Number of connectable
indoor units
Up to 6 units
Up to 4 units
Up to 2 units
❋
Refer the detail information
of installation
Maximum capacity of
connectable indoor
units
198 MBH
198 MBH
198 MBH
Installing the indoor units
Model
MCU-S6NEE1N
MCU-S4NEE1N
MCU-S4NEE2N
Example installing
Installing indoor units
The indoor unit’s capacity which is under 48 MBH, can be connected
in the MCU. Do not connect the indoor unit’s capacity exceeds
48 MBH.
Single capacity range under 36 MBH
- Connect the liquid, gas pipe of indoor unit to each single
port in MCU.
Single capacity range between 36 MBH to 48 MBH
- Join two ports in the MCU with offered Y-connector(liquid,
gas), then connect to indoor unit as above.
❋
Reference of continuous cooling.
In case of continuous cooling at below -5 °C(23 ˚F) ambient
condition, join two ports in the MCU with offered Y-connector, then
connect to indoor unit even though unit's capacity is between
18 MBH and 36 MBH.
Option switch and key function needs to be set. Detail information
refer the page 94 ~ 97.
The indoor unit’s capacity which
is greater than or equal to
36 MBH, can be connected in the
MCU. Do not connect the indoor
unit’s capacity not exceeding
36 MBH.
Single capacity range
between 36 MBH to
96 MBH.
- Join two ports in the
MCU with offered
Y-connector (liquid, gas),
then connect to indoor
unit as above.