ENGLISH-24
Refrigerant pipe installation
Choosing refrigerant pipe
H/P (AM038/048/055KXWD
✴
)
Size up for main pipe
First Y-joint
Pipe installation between an outdoor unit and the first Y-joint
Outdoor unit capacity [HP(Ton)]
Liquid pipe [mm (inch)]
Gas pipe [mm (inch)]
4 (3)
Ø9.52 (3/8)
Ø15.88 (5/8)
5 (4)
Ø9.52 (3/8)
Ø19.05 (3/4)
6 (5)
Ø9.52 (3/8)
Ø19.05 (3/4)
f
Install the refrigerant pipe according to main pipe size of each outdoor unit capacity.
Pipe installation between Y-joints
Indoor unit total capacity
[kW (Btu/h)]
1JQFEJBNFUFS 0t%tNN
Liquid pipe [mm (inch)]
Gas pipe [mm (inch)]
X ≤ 15.0 (51000)
Ø9.52 (3/8)
Ø15.88 (5/8)
15.0 (51000) < X ≤ 23.2 (79000)
Ø19.05 (3/4)