ENGLISH
E-
11
Performing Leak Test & Insulation
To check for gas leaks on the indoor unit, check the connec-
tion part of each refrigerant pipe by using a leak detector.
Once you have checked that there are no leaks in the system,
you can insulate the piping and hose.
To avoid condensation problems, place
T13.0 or thicker Acrylonitrile
Butadiene Rubber
around each refrigerant pipe.
1
Wind insulating tape around the pipes and drain hose.
2
Finish wrapping insulating tape around the rest of the pipes leading to the
outdoor unit.
3
Always make the seam of pipes face upwards.
Note
Leak Test
Insulation
Insulation
cover pipe
Be sure to overlap
the insulation
Indoor Unit
Insulation pipe
CAUTION
Must fit tightly against
body without any gap.
No gap
NBR(T13.0 or thicker)
Connecting the Cables to the Outdoor Unit
Two electric cables must be connected to the outdoor unit.
The connection cord connecting the indoor unit to the outdoor unit
The power cable connecting the auxiliary circuit breaker to the outdoor unit
1.Remove the terminal board cover on the side of the outdoor unit.
2.Connect the connection cord and power cable to terminals as shown in the dia-
gram.
3.Connect the power cable to the auxiliary circuit breaker.
4.Replace the terminal board cover, carefully tightening the screw.
CAUTION
Keep the power cable and the connection cord in a steel
pipe to protect them against liquids, outside impacts and
so on.
Note:
The connect cables should be incert from the front,use rubber-wire to protect
the cables.
Use hold-wire to fasten the cables,ensure the cables can not touch the comp
and pipes