90
SAMSUNG ELECTRONICS
10-2-3 Indoor fan motor speed detecting error (BLDC fan)
Indoor display
7 SEG DISPLAY
DESCRIPTION
C154
Indoor fan error
: LAMP ON
: LAMP OFF
: LAMP BLINK
1. Checklist :
1) Is the indoor units fan motor properly connected with the connector(CN900)?
2) Is the AC voltage correct?
2. Troubleshooting procedure
NO
YES
Power off andSeparatetheFanmotorwire
from CN72 onIndoorPBA
ExchangetheFan
motor
YES
YES
NO
YES
YES
Doesthefanrotate?
Isthefanerrorappearedagain?
Isthereshortamong
eachpin #1~#6
Isthe voltage of CN72 #1-#3 over250Vdc
Isthe voltage of CN72
#3-#5 and #3-#6 within1Vdc~15Vdcduring
theoperation?
Restartafter power off.
Reassemblethe fanwireandinputthe poweragain
PBA problemorMotorproblem
Changethe PBA firstandcheck theoperation
Exchangethe Fanmotor
NO
NO
NO
Terminatethe
service
Follow thecheck procedure of Indoorunit
powersupply errorcheck
ExchangetheIndoorPBA