73
SAMSUNG ELECTRONICS
9-2 Communication Error
9-2-1 Communication Error
Indoor display
7 SEG DISPLAY
DESCRIPTION
C101/C102
Communication error(Indoor<->outdoor)
Outdoor display
1min. Time out Comm.
Abnormal Communication
: LAMP ON
: LAMP OFF
: LAMP BLINK
1. Checklist :
1) Is the cable between the indoor unit and outdoor unit connected correctly?
2) Isn't the power cable and communication cable cross?
2. Troubleshooting procedure
Restartafter power off.
Isthecommunicationerroroccurredagain?
NO
YES
Exchangetheindoorunit PBA.
Is theconnection of powercableand
communicationcablenormal?
Isthe powerisnormal?
(check theLED Lamp)
Isthecommunicationerroroccurredagain?
NO
YES
NO
YES
YES
NO
YES
Terminatetheservice.
Correct thewrong cable.
Exchangethe PBA of no powerunit
Terminatetheservice.
Exchangethe outdoorunit PBA.