Installing and connecting the drain hose of the outdoor unit

Frame

Ground

Estimated 

snow fall

Snow-proof hood

Bottom surface of outdoor unit

Drain hose

Drain hole

Drain plug

While heating, ice may accumulate. During the process of defrosting, check if condensation draining is adequate.  For adequate 

draining, do the following:

The outdoor unit is loaded with 

 R410A refrigerant. 

 

Do not vent R410A into atmosphere: it is a 

 

greenhouse gas,  covered by Kyoto Protocol, with a Global Warming Potential (GWP) = 1975. 

 

It may cause reduction of cooling capacity and malfunction. Refrigerant for air purging is not charged in the outdoor unit. 

Use Vacuum Pump as seen in the picture. 

1.  Insert the drain plug into the drain hole on the underside of the outdoor unit.

1.  Connect each assembly pipe to the appropriate valve on the outdoor unit and 

2. 

applying the following torque:

2.  Connect a drain hose to the drain plug.

3.  Ensure that condensation draining is adequate.

Drain hole

Drain plug

   To avoid drain plug from contacting the ground, secure gap between the 

ground and the bottom surface of the outdoor unit.

   In areas with heavy snow fall, piled snow could block the air intake.  

To avoid this incident, install a frame that is higher than estimated snow 

fall. In addition, install a snow-proof hood to avoid snow from piling on the 

outdoor unit.

   When installing, make sure there is no leakage. When recovering the refrigerant, ground the compressor 

 

before removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor works 

with the service valve open, the pipe inhales the air and it makes the pressure inside of the refrigerant cycle 

abnormally high. It may cause explosion and injury.

Purging the connected pipes

Outdoor unit

Indoor unit

Gas pipe side

Liquid pipe side

Outer Diameter Torque (kg

f•cm)

ø6.35 mm

140~170

ø9.52 mm

250~280

ø12.70 mm

380~420

ø15.88 mm

440~480

ø19.05 mm

990~1210

ø22.23 mm

990~1210

  Excessive torque can be cause of gas leakage.

   Make the electrical connection and leave the system into “stand by 

mode”. Do not turn on the system! 

This is necessary for better vacuum operation (full OPEN position of 

Electronic Expansion Valve - EEV -).

If using a multi system, install as described in the installation manual supplied with the outdoor unit.

MAX_XSA_IBIM_DB98-33747A_E.pdf

ENGLISH

Содержание AQV09USeries

Страница 1: ...Air Conditioner user installation manual imaginethe possibilities ThankyouforpurchasingthisSamsungproduct To receive more complete service please register your product at www samsung com register DB98...

Страница 2: ...nstallation plate 26 Connecting the assembly cable 27 Installing and connecting the assembly pipe ofthe indoor unit 29 Purging the indoor unit 30 Cutting or extending the pipe 30 Installing and connec...

Страница 3: ...unlight and water rain drops Do not installthis appliance in a location where gas may leak This may result inelectric shock or fire Never install the outdoor unit in a location suchas on a high extern...

Страница 4: ...o do so may result in electric shock or fire In the event of a gas leak such as propane gas LP gas etc ventilate immediately without touching the power plug Do not touch the appliance or power cord Do...

Страница 5: ...e product Do not drink the water from the air conditioner The water may be harmful to humans Do not apply a strong impact to the remote controller and do not disassemble the remote controller Do not t...

Страница 6: ...C 24 C 32 C Relative humidity 80 or less AQV09 12U AQV18U AQV09 12U AQV18U AQV09 12U AQV18U Heating 27 C or less Dry 16 C 10 C 46 C 32 C Internal protections via the unit control system This internal...

Страница 7: ...ENGLISH 7 Main parts Display Checking the nameof the parts MAX_XSA_IBIM_DB98 33747A_E pdf Air intake up and down Room temperature sensor Timer Auto Clean indic SPi indicator ator...

Страница 8: ...ndoor unit during operation Power Mode Set one of the 5 operating modes see pages 10 11 for instructions Auto Clean Auto clean function Dry inside of the indoor unit to get rid of odor Temp hr Increas...

Страница 9: ...this product Applicable in the European Union and other European countries with separate battery return systems This marking on the battery manual or packaging indicates that the batteries in this pr...

Страница 10: ...air conditioner will cool your room You can adjust the temperature and the fan speed to feel cooler in hot season If current outside temperatures are much higher than the selected indoor temperature...

Страница 11: ...d High Press the button to adjust thetemperature Auto You can adjust the desired temperature by 1 C within the range of 16 C 30 C Cool You can adjust the desired temperature by 1 C within the range of...

Страница 12: ...sition you prefer There is a potential risk of personal injury when the unit is mishandled Using theTurbo function e d o m l o o C n i e l b a l i a v a y l n o s i n o i t c n u f o b r u T e h t s s...

Страница 13: ...de is set less than 4 hours the operation will stop at the same time If the mode is set over 5 hours it will run asWake up stage from the last one hour before it stops g n i t a e h r o f C 3 2 C 1 2...

Страница 14: ...utton for hour andFanmin button for minute 3 PressTimeSetbutton again to active it 1 Press the button O 2 Press theTemphr or button andFanmin button to set the time You can set the time in hourly unit...

Страница 15: ...he temperature range limit to help you save energy while the air conditioner is operating in Cool mode PresstheSmartSaverbutton on the remote controllerwhile the air conditioneris operating in Cool mo...

Страница 16: ...mately 15 minutes Using theQuiet function You can reduce the noise generated from an indoor unit PresstheQuiet button on theremote controllerwhilethe air conditioneris operating in Cool Heat mode Quie...

Страница 17: ...lean the display using alkaline detergent Do not use sulfuric acid hydrochloric acid organic solvents such as thinner kerosene and acetone etc to clean the surface of the product or put any stickers o...

Страница 18: ...original position and close the front panel Dry theAi lter in aventilated area CleantheA ter with a vacuum cleaneror soft brush If dust istoo heavy rinse it with running water o n the usage and envir...

Страница 19: ...the air conditioner properly Type Description Every2 weeks Every3 months Every4 months Onceayear Indoor unit 1 Clean the condensate drain pan 2 Thoroughly clean the heat exchanger 2 Clean the condens...

Страница 20: ...dows Check if the air conditioner has just been turned on after stopping cooling heating operation In this case just a fan will run to protect the outdoor unit compressor Check if the pipe length is t...

Страница 21: ...nts set forth in the Operating limits table included in the manual shall immediately invalidate the warranty The air conditioner should be used only for the applications for which it has been designed...

Страница 22: ...units components must be accessible and that can be disassembled in conditions of complete safety either for people or things For this reason where it is not observed as indicated into the Installatio...

Страница 23: ...conditioner Avoid the g places to prevent malfunction of the unit Where there is machine oil Salty environment such as seaside areas Other special atmosphere areas 125mm or more 300mm or more 125mm or...

Страница 24: ...0 or more 300 or more The upper part of the outdoor unit and the air outlet is opposite the wall When the walls are blocking front and the rear side of the outdoor unit 300 or more 1500 or more Top vi...

Страница 25: ...vibration will not cause any Accessories The following accessories are supplied with the air conditioner The number of each accessory is indicated in parentheses Accessories inthe indoor unit case Acc...

Страница 26: ...le can be connected from the Right A Left B Underside_right C Rear_right or left D B A D C D Direction of pipe 1 Determine the position of the pipe and drain hose hole as seenin the picture and drill...

Страница 27: ...f you install the product in a place where it is not strong enough to withstand the product weight the unit could fall and cause injury Connecting the assembly cable When you install the unit make ref...

Страница 28: ...t g n i d n o p s e r r o c e h t h t i w d e l e b a l s i e r i w h c a E Indoor unit Outdoor unit 09 12 18 Indoor unit Outdoor unit Ground wire Green Yellow Ground wire Green Yellow End of the wire...

Страница 29: ...t pressure of at least 20700 kPa Under no circumstances must sanitary type copper pipe be used There are 2 refrigerantpipes of diameters The smaller one is for the liquid refrigerant The larger one is...

Страница 30: ...pe longer than 5 meters You must extend the assembly cable You must add refrigerantto the pipes otherwise the indoor unit may freeze Unscrew the caps Pipes Oblique Rough Burr Pipe cutter Pipe The rema...

Страница 31: ...ollow Ditch 5 6 applying the following torque 7 For further details on how to connect to the outdoor unit and purge the air refer to page 33 35 Correct Uneven Thickness Cracked Damaged Surface Incline...

Страница 32: ...bber capwith the plier 2 Detach the drain hoseby pulling it and turning to the left 3 hose and the outlet of the drain pan 4 Attach the rubber cap witha screwdriver by turning it to the right until it...

Страница 33: ...bottom surface of the outdoor unit In areas with heavy snow fall piled snow could block the air intake To avoid this incident install a frame that is higher than estimated snow fall In addition instal...

Страница 34: ...ce port capto thevalve and tighten themat the torque of 183kgf cmwith a torque wrench 8 Checkfor a gas leak paying particularattention to the 3 way valve s stem nuts and to the service port cap Refer...

Страница 35: ...egarding the refrigerant used Charging the refrigerant under conditions of liquid by usinga liquid pipe a Factory refrigerantcharge of the product see unit name plate b to the above information for th...

Страница 36: ...rding to page 33 35 After opening valves check leaks using a leak detector for refrigerant Pump down before disconnecting therefrigerant connections for unit repair removal or disposal Pump down is an...

Страница 37: ...et thedischarged air out properly 2 Fix theoutdoor unit in level to an appropriate support using anchor bolts 3 If the outdoor unit is exposed to strongwinds install shield plates around the outdoor u...

Страница 38: ...p operation of the air conditioner 6 Disconnect the pipes 3 PresstheAirswing button and checkthefollowing 4 PressthePower button to stop the operation 2 PresstheMode button to select Cool or Heat mode...

Страница 39: ...5 Apply heat to the contraction tube to contract it 6 After tubecontraction work is completed wrap it with the How to connect your extended power cables Tools Crimping plier Connectionsleeve mm Insula...

Страница 40: ...QUESTIONS OR COMMENTS COUNTRY CALL OR VISIT US ONLINE AT AUSTRALIA 1300 362 603 www samsung com MAX_XSA_IBIM_DB98 33747A_E pdf...

Отзывы: