28
Deciding on where to install the product
Space requirements
X
f
The space suggested below is based on operating condition of outdoor temperature of 35°C. If operating condition of
outdoor temperature is higher than 35°C, try to have more space.
X
f
Make sure to clear a passage for a person and air flow.
X
f
Observe the clearances and dimensions as seen below when installing the outdoor unit.
X
f
If you install several outdoor units at the same place, observe the space for ventilation and free airflow.
X
f
If the space for ventilation is insufficient, the air conditioner may not generate performance designed. Keep in mind that
SAMSUNG logo is located on the front side of outdoor unit.
AP80S0
✴
X
❖
When there are no tall obstacles around the outdoor unit.
X
f
Maximum height of the obstacle: Front – Below 1500mm / Air inlet – Below 500mm / Side – when there is no height
limit.
(Unit: mm)
❋
When the air outlet is opposite the wall
❋
When the air outlet is towards the wall
O
ver 150
O
ver 150
❋
When 3 sides of the outdoor unit are blocked by the
wall
❋
When the upper part of the outdoor unit and the air
outlet is towards the wall
O
ver 300
Over 500
Over 600
O
ver 150
❋
When the upper part of the outdoor unit and the air
outlet is opposite the wall
❋
When front and rear side of the outdoor unit is
towards the wall
O
ver 500
Over 300
O
ver 300
O
ver 1500
PAC_아프리카 중동향AP80S0A_IBIM_34514A-02_EN.indd 28