![Samsung AM056FN2DEH Series Скачать руководство пользователя страница 92](http://html1.mh-extra.com/html/samsung/am056fn2deh-series/html/samsung/am056fn2deh-series/am056fn2deh-series_service-manual_4744774092.webp)
Product Specifications
92
Samsung Electronics
Indoor Unit (cont.)
Model
AM140JNEPEH/EU
AM220JNEPEH/EU
AM280JNEPEH/EU
Power Supply
Φ, #, V, Hz
1,2,220-240,50
1,2,220-240,50
1,2,220-240,50
Mode
*1)
HP
HP
HP
Performance
Capacity
Cooling
*2)
kW
14.0
28.0
28.0
Btu/h
-
-
-
Heating
*3)
kW
8.9
17.4
17.4
Btu/h
-
-
-
Condensate (with High fan speed)
Liters/h
Power
Input
W
220
300
370
Running Current
A
1.6
2.2
3.0
Sound Level
Sound Pressure (High/Low)
*4)
dB(A)
48
52
56
Fan
Type
-
Sirocco Fan
Sirocco Fan
Sirocco Fan
Motor
Model
-
Type
-
BLDC
BLDC
BLDC
Output
W
Airflow Rate
H/M/L
m3/min
18
28
50
External Pressure
Min/Std/Max
mmAq
20
25
30
Refrigerant
Type
-
R410A
R410A
R410A
Control Method
-
EEV
EEV
EEV
Temperature Control
-
Micom&Thermistors
Micom&Thermistors
Micom&Thermistors
Safety Devices
-
Fuse
Fuse
Fuse
Piping
Connections
Liquid (Flare)
ø, mm
9.52
9.52
9.52
Gas (Flare)
ø, mm
15.88
22.22
22.22
Drain
ø, mm
VP25 (OD 32,ID 25)
VP25 (OD 32,ID 25)
VP25 (OD 32,ID 25)
Weight
Net Weight
kg
51
85
85
Shipping Weight
kg
61
95
95
Dimensions
Net Dimensions (W x H x D)
mm
1110x390x650
1240x470x1040
1240x470x1040
Shipping Dimensions (W x H x D)
mm
1335x512x829
1507x558x1155
1507x558x1155
Functions
Auto Restart
-
O
O
O
Auto Swing
-
X
X
X
Group/Individual Control
-
O
O
O
External Contact Control
-
O
O
O
Trouble Shooting by LED
-
O
O
O
Standard
Accessories
Installation Manual
-
O
O
O
Operation Manual
-
O
O
O
Pattern Sheet for Installation
-
O
O
O
Flexible Drain Hose
-
X
X
X
Filter / Safety Grille
-
X
X
X
Optional
Accessories
Wireless Remote Controller
-
DMS 2.0
-
MIM-D00AN
MIM-D00AN
MIM-D00AN
Wired Remote
Controller
Simplified
-
MWR-WE10N
MWR-WE10N
MWR-WE10N
EHS
MWR-WW00N
MWR-WW00N
MWR-WW00N
External Contact Interface Module
-
MIM-B14
MIM-B14
MIM-B14
Drain Pump
MDP-N047SNC0D
ADP-N047SNC1D
ADP-N047SNC1D
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.
■
Fresh Air Duct
Содержание AM056FN2DEH Series
Страница 526: ...PCB Diagram and Parts List 526 Samsung Electronics 5 1 4 360 cassette MAIN PCB 1 2 3 4 5 6 7 8 9 10 11 12 13...
Страница 540: ...PCB Diagram and Parts List 540 Samsung Electronics 5 1 11 Duct type HSP BLDC PCB AM112 128 140FNHDEH 1 2 3 4...
Страница 593: ...PCB Diagram and Parts List Samsung Electronics 593 OAP DUCT AM220 280 NEPEH EU Cont BLDC Driver PCB cont 6 5 4 3 2 1...
Страница 643: ...Wiring Diagram Samsung Electronics 643 AMSSSMNFDEHS This Document can not be used without Samsung s authorization...
Страница 654: ...654 Samsung Electronics 6 1 27 OAP Duct AM140MNEPEH EU This Document can not be used without Samsung s authorization...
Страница 655: ...Samsung Electronics 655 6 1 28 OAP Duct AM140MNEPEH EU This Document can not be used without Samsung s authorization...
Страница 656: ...656 Samsung Electronics 6 1 29 OAP DUCT AM220 280 NEPEH EU This Document can not be used without Samsung s authorization...
Страница 657: ...Samsung Electronics 657 6 1 30 V AHU AMSSSJNZDCHS This Document can not be used without Samsung s authorization...
Страница 660: ...660 Samsung Electronics AM280JNPDKH TK AM280RNPDKH EU This Document can not be used without Samsung s authorization...