Product Specifications
Samsung Electronics
59
Indoor Unit (cont.)
■
Wall mounted type(Boracay with EEV)(cont.)
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.
Model
AM007KNQDCH/TC
AM009KNQDCH/TC
AM012KNQDCH/TC
Power Supply
ø, #, V, Hz
1,208~230,60
1,208~230,60
1,208~230,60
Mode
-
HP / HR
HP / HR
HP / HR
Performance
Capacity
(Nominal)
Cooling
2)
kW
-
-
-
Btu/h
7,500
9,500
12,000
Heating
2)
kW
-
-
-
Btu/h
8,500
10,500
13,500
Condensate
(with high fan speed)
Liter/h
-
-
-
Power
Input
W
30
39
42
Running Current
A
0.18
0.21
0.22
Sound Level Sound Pressure *4)
dB(A)
36
35
41
Fan
Type
-
Crossflow Fan Ф94*L601
Crossflow Fan Ф94*L601
Crossflow Fan Ф94*L601
Motor
Model
-
Y4S476B038L
Y4S476B038L
Y4S476B038L
Type
-
SSR Feedback
SSR Feedback
SSR Feedback
Output
W
-
-
-
Airflow Rate
Cooling (High)
m3/min
6.2
6.7
8.1
Heating (High)
m3/min
7.1
7.4
8.5
Refrigerant
Type
-
R410a
R410a
R410a
Control Method
-
EDM EEV 1.3C
EDM EEV 1.3C
EDM EEV 1.3C
Temperature Control
-
Micom&Thermistors
Micom&Thermistors
Micom&Thermistors
Safety Devices
-
Fuse:1.6A
Fuse:1.6A
Fuse:1.6A
Piping
Connections
Liquid (Flare)
ø, mm
6.35
6.35
6.35
Gas (Flare)
ø, mm
12.7
12.7
12.7
Drain
ø, mm
ID 18 hose
ID 18 hose
ID 18 hose
Weight
Net Weight
kg
8.5
9.0
9.0
Shipping Weight
kg
10.0
10.5
10.5
Dimensions
Net Dimensions (W x H x D)
mm
820*285*227
820*285*227
820*285*227
Shipping Dimensions
(W x H x D)
mm
880*280*363
880*280*363
880*280*363
Functions
Auto Restart
-
O
O
O
Auto Swing
-
O
O
O
Group/Individual Control
-
O
O
O
External Contact Control
-
O
O
O
Trouble Shooting by LED
-
O
O
O
Standard
Accessories
Installation Manual
-
O
O
O
Operation Manual
-
O
O
O
Pattern Sheet for Installation
-
X
X
X
Flexible Drain Hose
-
O
O
O
Filter / Safety Grille
Filter (Washable)
Filter (Washable)
Filter (Washable)
Optional
Accessories
Wireless Remote Controller
-
MR-EH00
MR-EH00
MR-EH00
Wired Remote
Controller
Simplified
-
MWR-WE10N
MWR-WE10N
MWR-WE10N
External Contact Interface
Module
-
MIM-B14
MIM-B14
MIM-B14
Содержание AM056FN2DEH Series
Страница 526: ...PCB Diagram and Parts List 526 Samsung Electronics 5 1 4 360 cassette MAIN PCB 1 2 3 4 5 6 7 8 9 10 11 12 13...
Страница 540: ...PCB Diagram and Parts List 540 Samsung Electronics 5 1 11 Duct type HSP BLDC PCB AM112 128 140FNHDEH 1 2 3 4...
Страница 593: ...PCB Diagram and Parts List Samsung Electronics 593 OAP DUCT AM220 280 NEPEH EU Cont BLDC Driver PCB cont 6 5 4 3 2 1...
Страница 643: ...Wiring Diagram Samsung Electronics 643 AMSSSMNFDEHS This Document can not be used without Samsung s authorization...
Страница 654: ...654 Samsung Electronics 6 1 27 OAP Duct AM140MNEPEH EU This Document can not be used without Samsung s authorization...
Страница 655: ...Samsung Electronics 655 6 1 28 OAP Duct AM140MNEPEH EU This Document can not be used without Samsung s authorization...
Страница 656: ...656 Samsung Electronics 6 1 29 OAP DUCT AM220 280 NEPEH EU This Document can not be used without Samsung s authorization...
Страница 657: ...Samsung Electronics 657 6 1 30 V AHU AMSSSJNZDCHS This Document can not be used without Samsung s authorization...
Страница 660: ...660 Samsung Electronics AM280JNPDKH TK AM280RNPDKH EU This Document can not be used without Samsung s authorization...