Troubleshooting
436
Samsung Electronics
4-4-15 The operational error of Indoor Unit's Fan Motor
1. How to diagnose
1) Occurs when RPM valve fails to feedback to MICOM at a PID control-type fan motor
2. How to check
1) Check HALL IC connector that carries out feedback of RPM value.
2) If a fan motor operation capacitor is a PCB separating type, check the connection terminal.
3) Check the operational status of the fan motor.
4) If there is no problem with the above checkup items, replace the PCB.
Outdoor unit display
x x x(x x x : The address of the error occurred indoor unit)
Indoor unit display
Criteria
• Refer to the judgment method below.
Cause of problem
• The operational error of the fan motor of No. XXX indoor unit
Содержание AM056FN2DEH Series
Страница 526: ...PCB Diagram and Parts List 526 Samsung Electronics 5 1 4 360 cassette MAIN PCB 1 2 3 4 5 6 7 8 9 10 11 12 13...
Страница 540: ...PCB Diagram and Parts List 540 Samsung Electronics 5 1 11 Duct type HSP BLDC PCB AM112 128 140FNHDEH 1 2 3 4...
Страница 593: ...PCB Diagram and Parts List Samsung Electronics 593 OAP DUCT AM220 280 NEPEH EU Cont BLDC Driver PCB cont 6 5 4 3 2 1...
Страница 643: ...Wiring Diagram Samsung Electronics 643 AMSSSMNFDEHS This Document can not be used without Samsung s authorization...
Страница 654: ...654 Samsung Electronics 6 1 27 OAP Duct AM140MNEPEH EU This Document can not be used without Samsung s authorization...
Страница 655: ...Samsung Electronics 655 6 1 28 OAP Duct AM140MNEPEH EU This Document can not be used without Samsung s authorization...
Страница 656: ...656 Samsung Electronics 6 1 29 OAP DUCT AM220 280 NEPEH EU This Document can not be used without Samsung s authorization...
Страница 657: ...Samsung Electronics 657 6 1 30 V AHU AMSSSJNZDCHS This Document can not be used without Samsung s authorization...
Страница 660: ...660 Samsung Electronics AM280JNPDKH TK AM280RNPDKH EU This Document can not be used without Samsung s authorization...