Product Specifications
Samsung Electronics
63
Indoor Unit (cont.)
■
Floor Standing Type
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.
Model
AM036FNFDEH/EU
AM056FNFDEH/EU
AM071FNFDEH/EU
Power Supply
Ø,V,Hz
220 - 240 V~ 50Hz
220 - 240 V~ 50Hz
220 - 240 V~ 50Hz
Mode
HP / HR
HP / HR
HP / HR
Performance Capacity
Cooling
kW
3.6
5.6
7.1
Btu/h
12,200
19,100
24,200
Heating
kW
4.0
6.3
8.0
Btu/h
13,600
21,400
27,200
Power
Running Current
Cooling
A
0.24
*5)
0.53
*5)
0.53
*5)
Heating
A
0.24
*5)
0.53
*5)
0.53
*5)
Input
Cooling
W
50.0
*5)
110.0
*5)
110.0
*5)
Heating
W
50.0
*5)
110.0
*5)
110.0
*5)
Sound Level
Sound Pressure
dB
43.0
45.0
45.0
FAN
Type
-
Sirocco
Sirocco
Sirocco
Motor
Model
-
OS-KRD306(KR035)
OS-KRD306A(KR045)
OS-KRD306A(KR045)
Airflow Rate
Cooling(High)
㎥
/min
10.0
*5)
16.5
*5)
16.5
*5)
Heating(High)
㎥
/min
11.0
*5)
19.0
*5)
19.0
*5)
Refrigerant
Type
-
R410
R410
R410
Control Method
-
EEV
EEV
EEV
Temperature Control
-
Micom & Thermistors
Micom & Thermistors
Micom & Thermistors
Safety Devices
-
Fuse
Fuse
Fuse
Piping
connections
Liquid(Flare)
Ø,mm
6.35
6.35
9.52
Gas(Flare)
Ø,mm
12.70
12.70
15.88
Drain
Ø,mm
ID18 HOSE
ID18 HOSE
ID18 HOSE
Weight
Net Weight
kg
23.0
28.5
28.5
Shipping Weight
kg
27.0
33.3
33.3
Dimensions
Net Dimensions
㎜
945x600x220
1225x600x220
1225x600x220
Shipping Dimensions
㎜
1035x690x310
1335x690x310
1335x690x310
Functions
Auto Restart
-
O
O
O
Auto Swing
-
X
X
X
Group/Individual Control
-
O
O
O
External Contact Control
-
O
O
O
Trouble Shooting by LED
-
O
O
O
Standard
Accessories
Installation Manual
-
O
O
O
Operation Manual
-
X
X
X
Pattern Sheet for Installation
-
X
X
X
Flexible Drain Hose
-
O
O
O
Filter / Safety Grille
-
O
O
O
Drain Pump
(Pumping, Speeed, Lift)
ℓ/h,mm
X
X
X
Optional
Accessories
Wireless Remote Controller
-
X
X
X
Wired Remote Controller
-
MWR-WE10N
MWR-WE10N
MWR-WE10N
External Contact Interface
Module
-
X
X
X
Содержание AM056FN2DEH Series
Страница 526: ...PCB Diagram and Parts List 526 Samsung Electronics 5 1 4 360 cassette MAIN PCB 1 2 3 4 5 6 7 8 9 10 11 12 13...
Страница 540: ...PCB Diagram and Parts List 540 Samsung Electronics 5 1 11 Duct type HSP BLDC PCB AM112 128 140FNHDEH 1 2 3 4...
Страница 593: ...PCB Diagram and Parts List Samsung Electronics 593 OAP DUCT AM220 280 NEPEH EU Cont BLDC Driver PCB cont 6 5 4 3 2 1...
Страница 643: ...Wiring Diagram Samsung Electronics 643 AMSSSMNFDEHS This Document can not be used without Samsung s authorization...
Страница 654: ...654 Samsung Electronics 6 1 27 OAP Duct AM140MNEPEH EU This Document can not be used without Samsung s authorization...
Страница 655: ...Samsung Electronics 655 6 1 28 OAP Duct AM140MNEPEH EU This Document can not be used without Samsung s authorization...
Страница 656: ...656 Samsung Electronics 6 1 29 OAP DUCT AM220 280 NEPEH EU This Document can not be used without Samsung s authorization...
Страница 657: ...Samsung Electronics 657 6 1 30 V AHU AMSSSJNZDCHS This Document can not be used without Samsung s authorization...
Страница 660: ...660 Samsung Electronics AM280JNPDKH TK AM280RNPDKH EU This Document can not be used without Samsung s authorization...