Troubleshooting
Samsung Electronics
4-101
4-4-76 Overvoltage / Low voltage error
Outdoor unit display
(INVERTER1 PCB)
(INVERTER2 PCB)
Judgment Method
· N-phase wiring error and EMI Fuse short.
· DC-Link Overvoltage / Low voltage occurs.
Cause of problem
· Check the input wiring
· EMI Fuse short
Power Off
Yes
Yes
380V is the voltage
between terminal blocks
R, S, T wire?
Power R, S, T, N wire voltage check and restart it.
Replace Inverter PCB and then restart it.
* Check the 3-phase sensing circuit part.
Replace Fuse, if the rectifier diode of
the inverter PCB is normal.
No
No
Did the EMI PCB Fuse is short?
1. Cause of problem