![Samsung AM009FN1DCH/AA Скачать руководство пользователя страница 130](http://html1.mh-extra.com/html/samsung/am009fn1dch-aa/am009fn1dch-aa_service-manual_4744782130.webp)
Troubleshooting
4-40
Samsung Electronics
4-4-13 The operational error of Indoor Unit's Fan Motor
×(Operation) ×(Timer)
◑
(Fan) ×(Filter) ×(Defrost)
x x x(x x x : The address of the error occurred indoor unit)
t
The operational error of the fan motor of No. XXX indoor unit
t
Refer to how to determine below
Indoor unit display
Criteria
Cause of problem
Outdoor unit display
1. How to diagnose
1) Occurs when RPM valve fails to feedback to MICOM at a PID control-type fan motor
2. How to check
1) Check HALL IC connector that carries out feedback of RPM value.
2) If a fan motor operation capacitor is a PCB separating type, check the connection terminal.
3) Check the operational status of the fan motor.
4) If there is no problem with the above checkup items, replace the PCB.
Содержание AM009FN1DCH/AA
Страница 214: ...PCB Diagram and Parts List Samsung Electronics 5 11 5 1 5 Duct type MSP 4 1 1 2 3 5 6 7 1 11 12 13 14 15 16 18 17 8 9 10...
Страница 216: ...PCB Diagram and Parts List Samsung Electronics 5 13 5 1 6 Duct type Super 1 2 3 5 4 6 9 10 11 12 13 14 15 16 7 8...
Страница 218: ...PCB Diagram and Parts List Samsung Electronics 5 15 5 1 7 Celing type 1 2 3 4 5 6 7 19 18 9 10 11 12 17 15 14 13 8...
Страница 224: ...Wiring Diagram Samsung Electronics 6 3 6 1 3 BIG Duct This Document can not be used without Samsung s authorization...
Страница 225: ...Wiring Diagram 6 4 Samsung Electronics 6 1 4 Ceiling This Document can not be used without Samsung s authorization...
Страница 226: ...Wiring Diagram Samsung Electronics 6 5 6 1 5 RAC Neo Forte This Document can not be used without Samsung s authorization...