Troubleshooting
Samsung Electronics
4-89
4-4-63 High Pressure Standard Not Met before Air Conditioning (Inability to Re-operate)
1. Cause of problem
Is High Pressure sensor connector
accurately connected to PCB?
Replace High Pressure sensor
Is there any refrigerant leakage or
recharging problem inside the system?
(Check it through Manifold gauge)
Reconnect and check connector.
No
No
Yes
Yes
Supplement or recharge the refrigerant.
Outdoor unit display
Indoorunit display
×(Operation)
ስ
(Reservation)
ስ
(Blast)
ስ
(Filter) ×(Defrost)
Judgment Method
. Operation should be forbidden if High Pressure sensor value of the Main Unit before the pump down is started at 2.2kg/cm²g
or below for air-conditioning and 1.0kg/cm²G or less for heating for three consecutive seconds.
(Restarting operation is not possible, and an error displayed on the indoor unit.)
Cause of problem
· Refrigerant leakage/fault in High Pressure sensor .
Содержание AM009FN1DCH/AA
Страница 214: ...PCB Diagram and Parts List Samsung Electronics 5 11 5 1 5 Duct type MSP 4 1 1 2 3 5 6 7 1 11 12 13 14 15 16 18 17 8 9 10...
Страница 216: ...PCB Diagram and Parts List Samsung Electronics 5 13 5 1 6 Duct type Super 1 2 3 5 4 6 9 10 11 12 13 14 15 16 7 8...
Страница 218: ...PCB Diagram and Parts List Samsung Electronics 5 15 5 1 7 Celing type 1 2 3 4 5 6 7 19 18 9 10 11 12 17 15 14 13 8...
Страница 224: ...Wiring Diagram Samsung Electronics 6 3 6 1 3 BIG Duct This Document can not be used without Samsung s authorization...
Страница 225: ...Wiring Diagram 6 4 Samsung Electronics 6 1 4 Ceiling This Document can not be used without Samsung s authorization...
Страница 226: ...Wiring Diagram Samsung Electronics 6 5 6 1 5 RAC Neo Forte This Document can not be used without Samsung s authorization...