25
Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Explanation
PAGE
MODE
Use of Auto Change
Over for HR only in
Auto mode
(When setting SEG3)
Standard heating
temp. Offset
(When setting SEG3)
Standard cooling
temp. Offset
(When setting SEG3)
Standard for mode
change
Heating
→
Cooling
Indication
and Details
Indication Details Indication Details Indication Details Indication
Details Indication Details Indication Details
0
5
0
Follow
product
option
0
0
0
0
0
1
1
Use Auto
Change
Over for
HR only
1
0.5
1
0.5
1
1.5
2
1
2
1
2
2
3
1.5
3
1.5
3
2.5
4
2
4
2
4
3
5
2.5
5
2.5
5
3.5
6
3
6
3
6
4
7
3.5
7
3.5
7
4.5
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Explanation
PAGE
(When setting SEG3)
Standard for mode
changing Cooling
→
Heating mode
(When setting SEG3)
Time required for
mode change
Compensation option
for Long pipe or height
diffference between
indoor units
Indication
and Details
Indication Details Indication Details Indication Details Indication
Details
1
0
1
0
5 min.
0
Use default
value
1
1.5
1
7 min.
1
1) Height
difference
1)
is more than
30m or
2) Distance
2)
is longer
than 110m
2
2
2
9 min.
3
2.5
3
11 min.
4
3
4
13 min.
2
1) Height
difference
1)
is
15~30m or
2) Distance
2)
is 50~110m
5
3.5
5
15 min.
6
4
6
20 min.
7
4.5
7
30 min.
05 series installation option(Detailed)