24
A
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
0
5
Use of Auto Change Over
for HR only in Auto mode
(When setting SEG3)
Standard heating temp.
Offset
(When setting SEG3)
Standard cooling temp.
Offset
(When setting SEG3)
Standard for mode change
Heating
→
Cooling
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
1
(When setting SEG3)
Standard for mode change
Cooling
→
Heating
(
When setting SEG3)
Time required for mode
change
C
ompensation option for
Long pipe or height
difference between
indoor units
-
-
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
2
-
-
-
-
Control variables when using
hot water / external heater
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
3
-
-
-
-
-
05 series installation option
Setting an indoor unit address and
installation option (Cont.)
*
Advanced function: Controlling cooling/heating current or power saving with motion detect.
(*1) Minimizing fan operation when thermostat is off
- Fan operates for 20 seconds at an interval of 5 minutes in heat mode.
(*2) 1: Fan is turned on continually when the hot water heater is turned on,
3: Fan is turned off when the hot water heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option,install the Mode Select switch(MCM-C200) on the outdoor unit and fix it as cool mode.
(*3) When the following 2 or 3 is used as external heater On/Off signal, the signal for monitoring external contact control will not be output.
2: Fan is turned on continually when the external heater is turned on,
3: Fan is turned off when the external heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option,install the Mode Select switch(MCM-C200) on the outdoor unit and fix it as cool mode.
·
If Fan is set to off for cooling only indoor unit by setting the SEG9=3 or SEG15=3, you need to use an external sensor or wired remote
controller sensor to detect indoor temperature exactly.
(*4) Default setting value
- 4Way Cassette, Mini 4Way Cassette: 5 °C
- Other indoor units: 2 °C
(*5) This function can be applied to 4 Way Cassette and Mini 4 Way Cassette only. If the air conditioner operates the heating mode
immediately after finishing the cooling mode, the condensated water in the drain pan becomes water vapor by the heat of the indoor
unit heat exchanger. Since the water vapor might be condensed on the indoor unit, which may fall into a living space, use this function to
get rid of the water vapor out of the indoor unit by operating the fan (for maximum 20 minutes) even when the indoor unit is turned off
after cooling mode is turned to heating mode .
Air Flow
Suction side
Discharge side
Electronic heater should
not be installed.
•
Do not install the electronic heater in the flow channel of the indoor unit fan.
Duct Indoor unit