20
A
Setting an indoor unit address and
installation option (Cont.)
1.
Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional
power supply in the indoor unit.
2.
The panel(display) should be connected to an indoor unit to receive option.
3.
Before installing the indoor unit, assign an address to the indoor unit according
to the air conditioning system plan.
Setting an indoor unit address (MAIN/RMC)
Option No. : 0AXXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Explanation
PAGE
Mode
Setting Main address
100-digit of indoor
unit address
10-digit of indoor
unit
The unit digit of
an indoor unit
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
0
A
0
No Main
address
0~9
100-digit
0~9
10-digit
0~9
A unit
digit
1
Main
address
setting
mode
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Explanation
PAGE
__
Setting RMC address
__
Group channel(*16)
Group address
Indication
and Details
Indication Details
Indication Details
Indication Details Indication Details
1
0
No RMC
address
RMC1
0~F
RMC2
0~F
1
RMC
address
setting
mode
Indoor Unit
1(L)
F2
F1
2(N)
4.
Assign an indoor unit address by wireless remote controller.
- The initial setting status of indoor unit ADDRESS(MAIN/RMC) is “0A0000-100000-200000-300000”.
When “A”~”F” is entered to SEG5~6, the indoor unit MAIN ADDRESS is not changed.
If you set the SEG 3 as 0, the indoor unit will maintain the previous MAIN ADDRESS even if you input the option value of SEG5~6.
If you set the SEG 9 as 0, the indoor unit will maintain previous RMC ADDRESS even if you input the option value of SEG11~12.
You cannot set SEG11 and SEG12 as F value at the same time.