38
Refrigerant pipe installation
f
Branch joint (E)
Select a branch joint according to the sum of indoor unit capacity which will be connected after the branch.
❋
However, if the size of the pipe between branch joints (E) is bigger than the size of the pipe connected to the outdoor unit
(D), apply the pipe size (D).
1) Y-joint
Classification
Model name
Specification [kW (MBH)]
Y-joint (E)
MXJ-YA1509M
15.0 kW (51.2 MBH) and below
MXJ-YA2512M
Over 15.0 kW ~ 40.0 kW (51.2 ~ 135.2 MBH) and below
MXJ-YA2812M
Over 40.0 kW ~ 45.0 kW (136.2 ~ 153.5 MBH) and below
MXJ-YA2815M
Over 45.0 kW ~ 70.3 kW (153.5 ~ 239.9 MBH) and below
MXJ-YA3419M
Over 70.3 kW ~ 98.4 kW (239.9 ~ 335.8 MBH) and below
MXJ-YA4119M
Over 98.4 kW ~ 135.2 kW (335.8 ~ 461.3 MBH) and below
MXJ-YA4422M
Over 135.2 kW (461.3 MBH)
2) Distribution
header
Classification
Model name
Specification [kW (MBH)]
Distribution header (E)
MXJ-HA2512M
45.0 kW (153.5 MBH) and below (for 4 rooms)
MXJ-HA3115M
70.3 kW (239.9 MBH) and below (for 8 rooms)
MXJ-HA3819M
Over 70.3 kW ~ 135.2 kW (239.9 ~ 461.3 MBH) and below
(for 8 rooms)