Outdoor unit combination
f
Make sure to use an indoor unit that is compatible with DVM S.
f
Indoor units can be connected within the range indicated in following table.
f
If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating capacity
of the indoor unit may decrease.
f
Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 ×
Σ
(Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 ×
Σ
(Outdoor unit capacity)
❋
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is set to 64
since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned from 0~63. If the
indoor unit address was assigned from 64~79, E201 error will occur.
❋
Maximum 32 Wall-mount type indoor units with EEV (AM
✴✴✴✴
NQDCH
✴
) can be connected.
t
Installation combination must be complied when composing outdoor unit combination.
CAUTION
Standard type (AM
✴✴✴
JXVAF
✴
Series)
Model name for combination
AM080JXVAFH/AZ AM100JXVAFH/AZ AM120JXVAFH/AZ AM140JXVAFH/AZ AM160JXVAFH/AZ
Number of individual outdoor units
1
1
1
1
1
Combined outdoor unit
AM080JXVAFH
1
AM100JXVAFH
1
AM120JXVAFH
1
AM140JXVAFH
1
AM160JXVAFH
1
AM180JXVAFH
AM200JXVAFH
Rated capacity
Cooling (kW)
22.4
28.0
33.6
40.0
45.0
Cooling (Btu/h)
76 400
95 500
114 600
136 500
153 500
Heating (kW)
25.2
31.5
37.8
45.0
50.4
Heating (Btu/h)
86 000
107 500
129 000
153 500
172 000
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW)
11.2
14.0
16.8
20.0
22.5
Minimum (Btu/h)
38 200
47 800
57 300
68 200
76 800
Maximum (kW)
29.1
36.4
43.7
52.0
58.5
Maximum (Btu/h)
99 400
124 200
149 000
177 400
199 600
Maximum number of connectable indoor
units
14
18
21
26
29