81
ENGLISH
Optional item
Input unit
SEG1 SEG2 SEG3 SEG4
Function of the option
Remarks
Energy control
Operaton
(B type PBA)
Main
1
0
0
0
Basic (Factory default)
Energy control option of
designated operation sequence
❋
Operating in energy saving
mode, capacity might
decrease compared to normal
operation mode
0
1
Energy saving
0
2
Power
Rotation defrost
(HR only)
Main
1
1
0
0
Disabled (Factory default)
0
1
Enabled
When enabled, continuous
heating operation is possible
but heating performance will
decrease during rotation defrost
operation
Expand
operational
temperature
range for cooling
operation (HR
only)
Main
1
2
0
0
Disabled (Factory default)
0
1
Enabled
When enabled, continuous
cooling operation is possible even
in low temperature condition up
to -15°C, but noise of the MCU will
increase
Channel address
Main
1
3
A
U
Automatic setting (Factory
default)
Address for classifying the
product from upper level
controller (DMS, S-NET 3, etc.)
0 ~ 15
Manual setting for channel
0~15
Snow
accumulation
prevention control
Main
1
4
0
0
Enabled (Factory default)
During snow accmulation , the fan
may spin even when the unit is
not in operation
0
1
Disabled
Unused option
Main
1
5
0
0
Unused option
Unused option by this model
Unused option
Main
1
6
0
0
Unused option
Unused option by this model
Speed operation
Main
1
7
0
0
Disabled (Factory default)
Enabling this setting will
command the air conditioner to
cool/heat faster at initial start-up
However, this function will not
work when High-head condition
setting or Long-piping condition
setting is enabled.
0
1
Enabled
Max. capacity
restriction
(B type PBA)
Main
1
8
0
0
Enabled (Factory default)
Restrict excessive capacity
increase when operating indoor
units with small capacity
0
1
Disabled
Gasleak
Pumpdown
(B type PBA)
Main
1
9
0
0
Disabled (Factory default)
If the gas leak occurred it should
be entered in the pumpdown
operation.
0
1
Enabled
Unused option
Main
2
0
0
0
Unused option
Unused option by this model
LA KIT option (B
type PBA)
Main
2
1
0
0
Disabled (Factory default)
Set when LA Kit is installed.
0
1
Enabled
Emergency
oeration for
indoor unit
communication
error (B type PBA)
Main
2
2
0
0
Disabled (Factory default)
When set, emergency operation
is possible even if an indoor
communication error occurs.
0
1
Indoor high humidity
condition (operation for up
to 12 hours)
0
2
Indoor low humidity
condition (operation for up
to 24 hours)
Base Heater (B
type PBA)
Main
2
3
0
0
Disabled (Factory default)
Set when Base Heater is installed.
0
1
Enabled