Things to check after completing the installation
1. Before supplying the power, use DC 500V (AM
✴✴✴✴
XVAJ
✴
) or DC 600 V (AM
✴✴✴✴
XVAF
✴
) insulation resistance
tester to measure the power (3 phase: R, S, T) terminal and the outdoor unit grounding.
- Measurement should be over 30MΩ.
2. Before supplying the power, use a voltmeter and phase tester to check the voltage and the phase.
- R, S, T terminal: Check the 460V (AM
✴✴✴✴
XVAJ
✴
) or 230V (AM
✴✴✴✴
XVAF
✴
) between wires (R-S, S-T, T-R)
T
S
R
T
S
R
<ELB>
[AM
✴✴✴
✴
XVAJ
✴
]
[AM
✴✴✴
✴
XVAF
✴
]
<ELB>
460V
230V
460V
230V
460V
230V
t
Never measure the communication terminal since communication circuit may get damaged.
t
Check for short-circuit of the communication terminal with a general circuit tester.
CAUTION
3. Check if the R-410A indoor units are connected.
4. Check the following after the installation is completed.
Installation work
Outdoor unit
t
Have you checked the external surface and the inside of the outdoor unit?
t
Is there any possibility of short-circuit caused by the heat of an outdoor unit?
t
Is the place well-ventilated and ensures space for service?
t
Is the outdoor unit fixed securely to withstand any external force?
Indoor unit
t
Have you checked the external surface and the inside of the indoor unit?
t
Is there enough space for service?
t
Have you checked if the center of the indoor unit is ensured and it is installed
horizontally?
Refrigerant pipe work
t
Have you selected correct pipes?
t
Are the liquid and gas valve open?
t
Is the total number of connected indoor units within the allowable range?
t
Are the length and the height difference between the refrigerant pipes
within the allowable range?
t
Are the branch joints properly installed?
t
Did you check the connection of liquid and gas pipes?
t
Have you selected correct insulator for pipes and insulated them correctly?
t
DId you insulate the pipes and connection part correctly?
t
Is the quantity of the additional refrigerant correctly weighed in? (You must
record the amount of additional refrigerant on the service record paper
placed inside of the outdoor unit.)
Drain pipe work
t
Have you checked if the drain pipes of the indoor and outdoor unit are
connected together?
t
Have you completed the drain test?
t
Is the drain pipe properly insulated?