Important information regulation
regarding the refrigerant used
This product contains fluorinated greenhouse gases. Do
not vent gases into the atmosphere.
CaUtIon
• Inform user if system contains 5 tCO
2
e or more
of fluorinated greenhouse gases. In this case, it
has to be checked for leakage at least once every
12 months, according to regulation n°517/2014.
This activity has to be covered by qualified
personnel only. In case situation above (5 tCO
2
e
or more of R-410A), installer (or recognized
person which has responsibility for final check)
has to provide a maintenance book, with all the
information recorded according to REGULATION (EU)
No 517/2014 OF THE EUROPEAN PARLIAMENT AND
OF THE COUNCIL of 16 April 2014 on fluorinated
greenhouse gases.
Please fill in the following indelible ink on the
refrigerant charge label supplied with this product on
and on this manual.
f
♳
: The factory refrigerant charge of the product.
f
♴
: The additional refrigerant amount charged in the
field.
f
♳
+
♴
: The total refrigerant charge.
Indoor unit
Outdoor unit
ⓓ
02
01
Unit
kg
tCo
2
e
♳
, a
♴
, b
♳
+
♴
, c
Refrigerant type
GWP value
R-410A
2088
• GWP = Global Warming Potential
• Calculating tCO
2
e : kg x GWP / 1000
notE
•
ⓐ
:
Factory refrigerant charge of the product: see
unit name plate.
•
ⓑ
:
Additional refrigerant amount charged in the
field. (Refer to the above information for the
quantity of refrigerant replenishment.)
•
ⓒ
:
Total refrigerant charge.
•
ⓓ
:
Refrigerant cylinder and manifold for charging.
CaUtIon
• The filled-out label must be adhered in the
proximity of the product charging port. (ex. onto
the inside of the stop valve cover.)