Setting key function
50
English
no.
option item
option
value
Factory
default
option
Definition
Setting unit
Module
control
setting
option
Note1)
5
Demand level
0 ~ 11
3
0
Default (100 %)
Main unit
of module
O
1
95 %
2
90 %
3
85 %
4
80 %
5
75 %
6
70 %
7
65 %
8
60 %
9
55 %
10
50 %
11
Not applied (No limit)
6
Quiet function input method
0·1
0
0
Module control/DMS
Main unit
of group
Note2)
1
External contact
7
Forced fan function input method
0·1
0
0
Module control/DMS
Main unit
of group
Note2)
1
External contact
8
Water law input method
0·1
0
0
Module control/DMS
Main unit
of group
Note2)
1
External contact
9
Pump operation when thermo off
0·1
1
0
Pump OFF when thermo OFF
and operation pattern is not
standard control.
Set key functions only when
the pumps are used for
each unit or water supply is
stopped to the unit whose
compressor does not work.
Main unit
of module
1
Pump ON always when
thermo OFF
10
Remote error reset input
0·1
0
0
Disuse
Main unit
of module
1
Use
11
Setting unit address
• Module address must be set.
(Refer to installation manual
of Module Control.)
0 ~ 15 (Not set)
Setting unit address
Each unit
12
Quiet function level
0 ~ 3
1
0
Default (100 %)
Main unit
of module
O
1
Level1
2
Level2
3
Level3
13
Confirm delay for unsecured
flow rate when operating
10 ~
240
30
Delay for inspecting no
input for pump interlock
and unsecured flow rate (by
seconds)
Main unit
of module
DB68-05916A-09_IM_DVM Chiller Outdoor_EU_EN_.indd 50