Electrical wiring work
34
English
Connecting the communication cable
UnIt 1
Module
control
F1 F2 V1 V2 F3 F4
UnIt2
UnIt 3
Protection
tube
Communication cable
Communication cable
Single connection
Module/Group connection
Hydro controller
communication part
Module
control
F1 F2 V1 V2 F3 F4
Communication cable (CHILLER)
UNIT 1
Module
control
UNIT 16
F1 F2 V1 V2 F3 F4
F1 F2 V1 V2 F3 F4
Communication cable (UNIT 1 ~ UNIT 16)
f
Communication cable between DVM CHILLERs has no polarity.
f
Fix the cable with a cable tie.
f
Maximum number of DVM CHILLER that can be controlled by a module control is 16.
terminal block
tightening torque (n·m)
6P T/B
M3.5
0.8 ~ 1.2
External contact wiring work
output contact
1
3
5
7
9
11
13
15
17
19
2
4
6
8
10
12
14
16
18
20
a-t/B
DB68-05916A-09_IM_DVM Chiller Outdoor_EU_EN_.indd 34
2022-05-02 오전 9:00:03