El
E
C
tRIC
al
W
o
RK
49
English
How to set hydro controller option
option no.
option value
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
operation on/off input
method
0
1
-
-
-
0
temperature setting input
method
0
2
-
-
-
0
1
Turn on the product.
2
Press and hold the K2 to enter the option setting.
f
In option setting, other key input (forced fan, temperature setting, etc.) is not received.
3
Press K1 shortly to display the number for selected option.
4
Press K2 shortly to display the number for set value of the selected option.
5
Finish the option setting.
f
Press K2 long to finish the setting with all option values determined and saved.
f
Press K1 long to finish the setting with all option values cancelled and keep the values as before entering the
setting.
• In option setting, press K4 long to initialize all option values.
no.
option item
option
value
Factory
default
option
Definition
Setting unit
Module
control
setting
option
Note1)
1
Operation On/Off input method
0·1
0
0
Module control/DMS
Main unit
of group
Note2)
1
External contact
2
Temperature setting input method
0·1
0
0
Module control/DMS
Main unit
of group
Note2)
1
External contact
3
Operation mode (Cool/Heat,
normal/hot water) input method
0·1
0
0
Module control/DMS
Main unit
of group
Note2)
1
External contact
4
Demand control input method
0·1
0
0
Module control/DMS
Main unit
of group
Note2)
1
External contact
DB68-05916A-09_IM_DVM Chiller Outdoor_EU_EN_.indd 49