Equipment for use in zone 2/zone 22
In equipment operated according to type of
protection Ex nA (non-sparking equipment)
according to EN 60079-15, circuits may be
connected, interrupted or switched while en-
ergized only during installation, mainte-
nance or repair.
The special conditions of use mentioned in
the statement of conformity are to be ob-
served for the rated values and the installa-
tion of the series-connected fuse for intercon-
nection of Ex nA circuits.
For Ex nA equipment (non-sparking equip
-
ment), circuits may be connected, interrupted
or switched while energized only during in-
stallation, maintenance or repair.
−
Positioners with type of protection Ex nA
or Ex tc can be used with a closed cover
(no window) or or with a cover with win-
dow.
−
The
(TROVIS SAFE
3730-61, 3730-65
and 3730-68 Positioners are 100 %
identical in design, except for the mark-
ing and the housing cover.
−
For type of protection Ex nA, the VCC
connection in the interface adapter must
be connected in series with a fuse ac-
cording to IEC 60127, 250 V F or T with
a fuse rating of I
N
≤40 mA.
−
The signal current circuit must be con-
nected in series with a fuse according to
IEC 60127-2/VI, 250 V T with a fuse
rating of I
N
≤63 mA.
−
The transmitter current circuit must be
connected in series with a fuse according
to IEC 60127-2/VI, 250 V T with a fuse
rating of I
N
≤40 mA.
The fuses must be installed outside the haz-
ardous area.
Cable entry
Cable entry with M20x1.5 cable gland, 6 to
12 mm clamping range.
There is a second M20x1.5 threaded hole in
the housing that can be used for additional
connection, when required. The screw termi-
nals are designed for wire cross-sections of
0.2 to 2.5 mm². Tighten the screws by 0.5 to
0.6 Nm.
The
wires for the set point
must be connect-
ed to the terminals 11 and 12 located in the
housing.
Only use a
current source
.
≥3.6 mA:
Microprocessor and display active
<3.7 mA:
LOW reading on display
≤3.8 mA:
Emergency shutdown (version with
shutdown at 3.8 mA)
>3.9 mA:
Actuator can be filled with air
(version with shutdown at 3.8 mA)
≤4.4 mA:
Emergency shutdown (version with
shutdown at 4.4 mA)
>4.6 mA:
Actuator can be filled with air
(version with shutdown at 4.4 mA)
>22 mA:
OVERLOAD reading on display
Содержание TROVIS SAFE 3730-6
Страница 12: ...12 EB 8384 6S EN...
Страница 16: ...16 EB 8384 6S EN...
Страница 22: ...22 EB 8384 6S EN...
Страница 40: ...40 EB 8384 6S EN...
Страница 42: ...42 EB 8384 6S EN...
Страница 82: ...82 EB 8384 6S EN...
Страница 90: ...90 EB 8384 6S EN...
Страница 96: ...96 EB 8384 6S EN...
Страница 132: ...132 EB 8384 6S EN...
Страница 152: ...152 EB 8384 6S EN...
Страница 155: ...EB 8384 6S EN 155...
Страница 156: ...156 EB 8384 6S EN...
Страница 157: ...EB 8384 6S EN 157...
Страница 158: ...158 EB 8384 6S EN...
Страница 159: ...EB 8384 6S EN 159...
Страница 160: ...160 EB 8384 6S EN...
Страница 161: ...EB 8384 6S EN 161...
Страница 162: ...162 EB 8384 6S EN...
Страница 163: ...EB 8384 6S EN 163...
Страница 164: ...164 EB 8384 6S EN...
Страница 165: ...EB 8384 6S EN 165...
Страница 166: ...166 EB 8384 6S EN...
Страница 167: ...EB 8384 6S EN 167...
Страница 182: ...182 EB 8384 6S EN...
Страница 183: ...EB 8384 6S EN 183...