Functions and parameters
When the binary input is active, the current input cannot be used.
Functions
WE
Configuration
F05: Current input
0
F05 - 0
F08: Function of binary input
0
F08 - 0
2.4
Excessive temperature protection
The actuator closes the valve when the flow temperature at the flow sensor exceeds the upper
limit (GWH).
When F10 - 0 is configured,
no
monitoring of the flow temperature for violation of the upper
limit takes place.
Functions
WE
Configuration
F10: Upper limit (GWH)
0
F10 - 1
Parameters
WE
Value range
P05: Upper limit (GWH)
95 °C
0 to 100 °C
2.5
Frost protection
When the function is active, the flow temperature is monitored for violation of the lower limit.
When the temperature falls below the
lower limit (GWL)
, the actuator opens the valve (puls-
es) until the temperature exceeds the lower limit plus hysteresis.
When F11 - 0 is configured,
no
monitoring of the flow temperature for violation of the lower
limit takes place.
Functions
WE
Configuration
F11: Lower limit (GWL)
0
F11 - 1
Parameters
WE
Value range
P06: Lower limit (GWL)
5 °C
0 to 20 °C
NOTICE
!