Configuration list and customer settings
F
Function
WE Meaning
16
Function of switching out
-
put
3
1: Not active
2: Fault alarm
3: Circulation pump (DHW)
4: Circulation pump (heating)
5: Tapping
6: Circulation pump (heating) reversed
1)
17 Pump protection
1)
1
0: No
1: Yes
1)
Firmware version 2.20 and higher
Parameter list
The parameters have the setting ranges as listed below.
P = Parameter
WE = Default setting
P
Parameters
WE
Adjustment range
01
Set point W1
60 °C
0 to 100 °C
02
Set point W2
70 °C
0 to 100 °C
03
Lower measuring range value Xmin
0 °C
–50 to 90 °C
04
Upper measuring range value Xmax
100 °C
10 to 150 °C
05
Upper limit (GWH)
95 °C
0 to 100 °C
06
Lower limit (GWL)
5 °C
0 to 20 °C
07
Proportional-action coefficient KP
0.8
0.1 to 50
08
Reset time Tn
15 s
0 to 999 s
09
Derivative-action time Tv
0 s
0 to 999 s
10
Actuator transit time Ty
25 s
0 to 240 s
11
Set-back difference
8 K
0 to 30 K
12
Heating period to maintain heat exchanger at
constant temperature
1)
24.0 h
0 to 25.5 h
1)
Firmware version 2.20 and higher