![Samson TROVIS 5757-3 Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/samson/trovis-5757-3/trovis-5757-3_configuration-manual_4068827005.webp)
KH 5757 EN
5
Functions and parameters
2
Functions and parameters
2.1
DHW heating in instantaneous heating system
Zir
KW
VL RL
WW
WSS
VS
TW
W
VS
TW
DHW sensor
RL
District heating return flow WW Hot water
WSS Water flow sensor
VL
District heating supply
KW
Cold water
Zir
Circulation pipe
Fig. 1:
DHW heating in instantaneous heating system with flow sensor and DHW tapping
recognition
The DHW temperature is controlled to the set point temperature in DHW heating in instanta-
neous heating systems:
Î
If the DHW temperature falls below the set point, the actuator opens the valve (pulses) to
increase the DHW temperature.
Î
If the DHW temperature exceeds the set point, the actuator closes the valve (pulses) to
reduce the DHW temperature.
Functions
WE
Configuration
F01: DHW tapping recognition
1
F01 - 0
Parameters
WE
Value range
P01: Set point W1
60 °C
0 to 100 °C
P02: Set point W2
70 °C
0 to 100 °C