Functions and parameters
2.8
Function of switching output
The switching output function is available for electric actuators with firmware 2.x and higher.
The switching output can be configured as either a pump output (circulation pump for the
DHW circuit or heating circuit), a fault alarm output or an output to report when hot water is
tapped.
−
Passive function:
The switching output is inactive.
−
Function of the fault alarm:
The switching output is active when a fault has
occurred.
−
Function of the circulation pump
(DHW):
The switching output is active while hot water is
being tapped, when the function to maintain the hot
water at a constant temperature or the frost
protection function is active.
−
Function of the circulation pump
(heating):
The switching output is active after a demand for
heat (valve position > 0 %).
−
Function of the tapping:
The switching output is active while hot water is
being tapped.
−
Function of the circulation pump
(heating) reversed:
The switching output is switched off when the
actuator stem reaches the top end position.
Functions
WE
Configuration
F16: Function of switching output
1
F16 - 1: Not active
F16 - 2: Fault alarm
F16 - 3: Circulation pump (DHW)
F16 - 4: Circulation pump (heating)
F16 - 5: Tapping
F16 - 6: Circulation pump (heating) reversed
NOTICE
!