Functions and parameters
2.6
Control parameters
Parameters
WE
Value range
P07: Proportional-action coefficient KP
0.8
0.1 to 50
P08: Reset time Tn
15 s
0 to 999 s
P09: Derivative-action time Tv
0 s
0 to 999 s
P10: Actuator transit time Ty
25 s
0 to 240 s
The actuator transit time
Ty actuator transit time for valve travel
(P10) reflects the time that the
valve needs to move through the range from 0 to 100 % without stopping. The default setting
is 25 s.
The default setting is based on the rated travel of 6 mm. The actual transit time can be deter
-
mined by the "Start transit time measurement" parameter. See section 4.4.
2.7
External demand processing
The device can process an external demand for heat depending on the configuration. A
measuring range (Xmin to Xmax) is assigned to the current signal (0 to 20 mA or 4 to
20 mA, set point). The external hot water set point has priority over the internal set point.
Only a Pt 1000 sensor can be used to measure the hot water temperature when the function
for an external demand is active.
Functions
WE
Configuration
F05: Current input
0
F05 - 1
F06: Function of current input
0
F06 - 1
F07: Measuring range of current input
0
F07 - 0: 0 to 20 mA
F07 - 1: 4 to 20 mA
Parameters
WE
Value range
P03: Lower measuring range value Xmin
0 °C
–50 to 90 °C
P04: Upper measuring range value Xmax
100 °C
10 to 150 °C
NOTICE
!
NOTICE
!